Appendix I. Using MD485 Multidrop Modems with AVW200 Interfaces
'CR1000 Series Datalogger
'This program measures 2 sensors on 2 AVW200s PBA1 and PBA5.
'Each AVW200 is connected to a MD485 via a RS-232 null modem. The RS-232 baud rate of the MD485s
'is 38.4 k as is the RS-485 baud rate. The MD485s are set to Pakbus Network
'the Thermister reading is converted from Ohms to Deg C
Public PTemp, batt_volt
Public Dst(2,6)
Public TempC(2), TempK(2)
Public Rf(2)
Public result(2)
'ABC=temp coefficients for the Steinhart-Hart equation to convert Ohms to TempC
const A=.001403040
Const B=.000237318
const C=.00000009
DataTable (AVW200,1,-1)
DataInterval
(0,10,Sec,10)
Sample
(6,Dst(1,1),IEEE4)
Sample
(6,Dst(2,1),IEEE4)
EndTable
DataTable (AVWcard,1,-1)
CardOut
(0
,-1)
DataInterval
(0,10,Sec,10)
Sample
(6,Dst(1,1),IEEE4)
Sample
(6,Dst(2,1),IEEE4)
EndTable
BeginProg
SerialOpen (ComRS232,38400,0,0,10000)
Scan (10,Sec,0,0)
PanelTemp
(PTemp,250)
Battery
(Batt_volt)
'Result,
comport,neighbor,PBA,Dst,chan,muxchan,reps,begFreq,endFreq,Vx,IntegrationTime,Mult,Offset)
'sensor
1,
channel
1
AVW200(result(1),ComRS232,1,1,Dst(1,1),1,1,1,1000,3500,2,_60HZ,1,0)
'sensor
2,
channel
2
AVW200(result(2),ComRS232,5,5,Dst(2,1),1,1,1,1000,3500,2,_60HZ,1,0)
Rf(1)=Dst(1,6)
Rf(2)=Dst(2,6)
TempK(1) = 1/(A + B*LN(Rf(1)) + C*(LN(Rf(1)))^3)
TempK(2) = 1/(A + B*LN(Rf(2)) + C*(LN(Rf(2)))^3)
TempC(1)
=
TempK(1)-273.15
TempC(2)
=
tempK(2)-273.15
CallTable
avw200
CallTable
avwcard
NextScan
EndProg
I-5
Summary of Contents for AVW200 series
Page 2: ......
Page 78: ...Appendix C Antennas Antenna Cables and Surge Protectors for the AVW206 AVW211 and AVW216 C 8...
Page 86: ...Appendix E Status Table E 4...
Page 104: ...Appendix H Additional Programming Examples H 12...
Page 110: ...Appendix I Using MD485 Multidrop Modems with AVW200 Interfaces I 6...
Page 111: ......