Appendix I. Using MD485 Multidrop Modems with AVW200 Interfaces
Connects to another MD485 via
the CABLE2TP
Connects to the datalogger’s
RS-232 port or the AVW200’s
RS-232 port via a null modem cable
Connects to earth ground
via an 8 AWG wire
FIGURE I-4. MD485 and its connectors.
I.2.1 Datalogger to MD485
The 18663 Null Modem Cable is used to connect an MD485 with the CR800,
CR850, CR1000, or CR3000 datalogger. One end of the null modem cable
attaches to the RS-232 port on the MD485, and the other end attaches to the
RS-232 port on the datalogger (see Figure I-4).
I.2.2 MD485 to MD485
The connection between MD485s is made with a CABLE2TP two-twisted pair
cable with shield. Insulation colors are red/back and green/white. One pair is
used for the differential data (“A” connects to “A”, “B” connects to “B”), and
one line of the other twisted pair is used for the signal ground (third connection
on the MD485 terminal block). This is shown in Figures I-4 and I-5. The
cable shield should be connected to a chassis or earth ground (NOT the signal
ground) at one end as shown in Figure I-5.
I-3