EMC_SPEC040_CLCR.doc
Rev. E
–
2021 10 18
57/63
Install & Operating Manual
CleanSeal V3
PLEASE NOTE:
The actual direction of the probe movement will depend on the housing type
and the chosen installation orientation.
Refer to the sticker applied on installation for practical operator orientation,
see § 9.4.5
Generally :
•
Turn
CLOCKWISE
Probe moves
TOWARDS
the drive port
•
Turn
COUNTER-CLOCKWISE
Probe moves
AWAY
from the drive port
CAUTION:
When using a manual crank, turn lightly and
regularly, DO NOT force!
When using a power tool, limit drive torque
to 1 Nm
to avoid damaging the drive shaft
in the end positions.
A damaged drive shaft may be replaced without compromising the housing or filter installation,
using the Control Box as an access hatch,
see § 9.4.1
PLEASE NOTE:
The necessary rotational drive port speed R
for any required “scanning” speed
Vs
(sampling probe displacement) is calculated as follows :
(e.g.: Vs = 10 mm/s
➔
R = 200 rpm)
Drive tools for MIP operation can be obtained from Camfil.
➔
Power tool
MIP Driver
Ref. 1086894
𝑹 [𝒓𝒑𝒎] = 𝑽𝒔 [
𝒎𝒎
𝒔
] × 𝟐𝟎