9
Installation of Add-ons
9.1
Dampers
PLEASE NOTE:
The installation of either shut-off or regulation dampers as standard add-ons
requires
a “damper ready” S
-C-housing or a customized T-C-housing.
Interface parts like the adapter rod and locking screws are included as accessories
with the housing.
Dampers are packed separately from the housing.
➔
For shut-off dampers
discard fixing screws
➔
For regulation dampers
replace with
s washers
from damper accessory kit
and adjust to desired friction strength
➔
Adjust dampers from the technical area above
by turning the damper handle
or
➔
from the room below
by turning the adapter rod
2,5
M5
2,5
M5