10.1
Filter Compatibility
Any CleanSeal housing can be ordered with filter clamps preset for either MD, MX or MG
HEPA filter panels (frame heights 66 / 90 / 110 mm), or for 78 mm frame height.
Camfil Ecopleat filters with (recommended) or without gasket
at 98 / 96 mm filter height are also compatible with CleanSeal
housings. Use settings for MX (90 mm) and adjust,
see § 10.2
Camfil CleanSeal clamping presets are designed for filters with
6 … 7,5 mm foamed PU gasket
.
Other brand filters and/or gasket types may be used, referring
to the instructions in
, however, this may affect
installation integrity. If in doubt, contact your Camfil representative.
PLEASE NOTE :
Clamp settings can be changed, so the customer has the option of upgrading
to bigger filters for higher airflow or reduced pressure drop at any time,
see § 10.2
Prefilters
CleanSeal Exhaust wall (CR) and ceiling (CL) housings can accept an additional 48 / 50 mm G4 / G5 filter
in the optional prefilter door, which can be exchanged against the standard door at any time.
Gel Filter Compatibility
On request, all CleanSeal can be proposed for GEL fluid gaskets as well.
3 filter frame profiles are compatible
with CleanSeal Gel filters
(frame heights 71 / 105 / 115 mm),
corresponding to the 3 presets.
PLEASE NOTE :
130 mm frames are NOT compatible
with the standard housing chassis.
MX