24
Section 2
MC-III™ EXP Flow Analyzer
Pulse Output
The pulse output is a solid-state relay. Each pulse represents a user-defined volume. Because the circuit is
isolated, it can be used in conjunction with any other feature on the MC-III EXP. A two-conductor cable from
the MC-III EXP to the remote location is required (Figure 2.13). The maximum current rating of the pulse
output circuit is 60 mA at 30 VDC.
A Zener diode (Part No. 1.5KE56CA) must be installed for CE approval.
For information on configuring the pulse output with the keypad, see
Configuring the Pulse Output, page
For information on configuring the pulse output with the interface software, see
TB1
PU
LS
E
IN
PU
T
RE
SE
T
IN
PU
T
TF
M
A&S
GND
TB
3
EXT POWER
TB2
RS4
85
SL
AV
E
4-2
0
OU
T
PU
LS
E
OU
T
6-3
0 V
DC
J1
J2
RESET
SWITCH
BA
TT
ER
Y
Leave this
end of shield
disconnected.
POWER SUPPLY
5 to 30 VDC
*
Resistor may be included in pulse readout
device. Size the resistor to limit the current
to 60 mA.
*
PULSE READOUT
DEVICE
Figure 2.13—Pulse output wiring
Summary of Contents for NUFLO MC-III EXP
Page 1: ...NUFLO TM MC III EXP Flow Analyzer User Manual Manual No 9A 50165003 Rev 06 Valves Measurement ...
Page 18: ...12 Section 1 MC III EXP Flow Analyzer ...
Page 35: ...29 MC III EXP Flow Analyzer Section 2 ...
Page 46: ...40 Section 3 MC III EXP Flow Analyzer ...
Page 81: ...75 MC III EXP Flow Analyzer Section 4 ...
Page 93: ...87 MC III EXP Flow Analyzer Section 5 Figure 5 17 Dropdown menu for exporting log data ...
Page 94: ...88 Section 5 MC III EXP Flow Analyzer ...
Page 105: ...99 MC III EXP Flow Analyzer Section 6 ...
Page 114: ...A 9 MC III EXP Flow Analyzer Appendix A ...
Page 121: ...B 7 MC III EXP Flow Analyzer Appendix B ...
Page 123: ...C 2 Appendix C MC III EXP Flow Analyzer ...
Page 141: ...D 18 Appendix D MC III EXP Flow Analyzer ...
Page 143: ......