20
Section 2
MC-III™ EXP Flow Analyzer
Field Wiring
The MC-III EXP supports connections for the following: internal power (battery), external power, turbine
flowmeter input, pulse input, remote reset input, pulse output, 4 to 20 mA output, flowmeter frequency (amp
& square) output, and RS-485 output.
Wiring diagrams for each connection are provided below.
Caution: For a CSA-approved MC-III EXP installed in a hazardous location, all field wiring must
conform to wiring methods for explosion-proof installations as defined in the
National Electric Code for installations within the United States or as specified in the
Canadian Electric Code for installations within Canada. State and local wiring
ordinances may also apply.
To wire the MC-III EXP for operation, complete the following field connections:
1. Unscrew the cover of the enclosure and remove it.
2.
Using a small standard blade screwdriver, remove the two #4-40 × 7/8” screws located to the right and
left side of the display.
3. Lift the display/keypad assembly from the enclosure, making sure the circuit assembly does not contact
the enclosure.
4.
Connect the lithium battery or alkaline battery pack to the J1 connector marked “BATTERY” near the top
of the circuit assembly.
5. Connect wiring for external power, if appropriate. See
.
6.
Connect the flowmeter or pulse input wiring to terminal block TB1. See
and
7. Connect wiring for the remote reset input to terminal block TB1, if appropriate. See
and
8. Connect wiring for output signals, if appropriate. See
Figure 2.13, page 24, through Figure 2.17, page 27.
9. Place the circuit assembly over the standoffs and fasten with the two #4-40 × 7/8” screws, ensuring that
all connector wiring is inside the enclosure and in no position where it may be damaged when the enclo-
sure cover is replaced.
10. Recalibrate the MC-III EXP (if necessary).
11. If external and internal power supplies were removed, reset the clock to ensure that the time stamps in the
log data are accurate. The clock is reset using the MC-III interface software. See
12.
Replace the enclosure cover.
Summary of Contents for NUFLO MC-III EXP
Page 1: ...NUFLO TM MC III EXP Flow Analyzer User Manual Manual No 9A 50165003 Rev 06 Valves Measurement ...
Page 18: ...12 Section 1 MC III EXP Flow Analyzer ...
Page 35: ...29 MC III EXP Flow Analyzer Section 2 ...
Page 46: ...40 Section 3 MC III EXP Flow Analyzer ...
Page 81: ...75 MC III EXP Flow Analyzer Section 4 ...
Page 93: ...87 MC III EXP Flow Analyzer Section 5 Figure 5 17 Dropdown menu for exporting log data ...
Page 94: ...88 Section 5 MC III EXP Flow Analyzer ...
Page 105: ...99 MC III EXP Flow Analyzer Section 6 ...
Page 114: ...A 9 MC III EXP Flow Analyzer Appendix A ...
Page 121: ...B 7 MC III EXP Flow Analyzer Appendix B ...
Page 123: ...C 2 Appendix C MC III EXP Flow Analyzer ...
Page 141: ...D 18 Appendix D MC III EXP Flow Analyzer ...
Page 143: ......