4H. FLOW CHECKING
Flow checking allows you to have the controller
compare the flow of each station during irrigation to
the learned expected flow and alert you of any
problems.
From the FLOW METER, MASTER VALVE & PUMP
SETUP screen (Figure 4.1).
1.
Press the
FLOW CHECKING
Menu
key
The FLOW CHECKING screen is displayed
(Figure 4.16).
flow rate to the expected? No
FLOW CHECKING
When Irrigating COMPLARE the
Figure 4.16
This will open up the ALLOWABLE portion of the
screen when you select YES to the WHEN
IRRIGATING COMPARE THE FLOW TO THE
EXPECTED ? question (Figure 4.17).
flow rate to the expected? YES
FLOW CHECKING
When Irrigating COMPLARE the
ALLOWABLE
Below 30 gpm - 5 / + 5
From 65 gpm to 100 gpm - 10 / + 10
( - gpm / + gpm )
From 30 gpm to 65 gpm - 10 / + 10
Above 100 gpm - 15 / + 15
Figure 4.17
2.
Press the blue
ARROW
keys to
change the Allowable settings
.
The default settings are:
BELOW: -5 / +5
FROM / TO: -10 / +10
FROM / TO: -10 / +10
ABOVE: -15 / +15
Note:
The above settings are defaulted in the
controller and can be changed by the user.
3.
To change the settings press the
PLUS
or
MINUS
keys for any number
to change the setting.
Below:
This section allows you to enter the
fluctuation range for the low end of your normal
operating flow. Use the (-) and (+) entries to set the
range.
Example:
If you set the below limit at 30 gallons per minute.
and set your limit at -5/+5,
You will be alerted if the flow at the low end of the
scale fluctuates by more than 5 gallons per minute
in either direction.
That is less than 25 gpm or more than 35 gpm
1
st
From / To:
This section allows you to set the
fluctuation limits for the lower range of your medium
flowing valves. In this box you want to enter the
normal operating range of water flow. Then in the (-)
and (+) blocks enter the range of fluctuation that you
deem normal.
Example:
If you set the below limit at 30 gpm to 65 gpm.
and set your limit at -10/+10,
You will be alerted if the flow at the low end of the
scale fluctuates by more than 10 gallons per
minute in either direction.
That is less than 20 gpm or more than 75 gpm
2nd From / To:
This section allows you to set the
fluctuation limits for the high end of your medium
flowing valves. In this box you want to enter the
normal operating range of water flow. Then in the (-)
and (+) blocks enter the range of fluctuation that you
deem normal.