I-MAT_Ed6 - Operating Instructions
Page 41 / 164
9.4.2.
Constant temperature mode with 2
temperature transducers (differential
mode)
If it is required to use a differential pressure
feedback, between delivery and suction of the pump
by using 2 transducers it’s necessary to connect
the first transducer and the second transducer as
shown in section 6.7.
Parameters to programm or check (recommended
sequence):
Par.
Description
Suggested value
AP02
Primary transducer supply
data sheet
transducer
AP03
Primary transducer
measuring unit
4 [°C]
AP04
Primary transducer
minimum value
data sheet
transducer
AP05
Primary transducer
maximum value
data sheet
transducer
AP06
Secondary transducer
supply
data sheet
transducer
AP07
Secondary transducer
measuring unit
4 [°C]
AP08
Secondary transducer
minimum value
data sheet
transducer
AP09
Secondary transducer
maximum value
data sheet
transducer
AP10
Secondary transducer
mode
DiFF
UP02
Nominal pump current
see motor plate
UP03
Nominal pump frequency
see motor plate
UP05
Operating mode
tC
UP06
Primary set-point
on demand [°C]
tC01
System type
HEAt/Cool
9.4.3.
Automatic pump stop at minimum
frequency.
In this operating mode typically the pump runs
continuously without stop. If it is required to stop the
pump when it’s working at the minimum operating
frequency (parameter SA03) it’s necessary to
change the value of the parameter AP16 from “Off”
to “FM”.
The system will restart when the temperature of the
system will reach the value of parameter tC02.
9.5. Constant flow operating mode.
Constant flow rate mode keeps constant the flow in
a point of the system.
This configuration uses a feedback given by a flow
sensor (connected as shown in section 6.7).
Parameters to programm or check (recommended
sequence):
Par.
Description
Suggested value
AP02
Primary transducer supply
data sheet
transducer
AP03
Primary transducer
measuring unit
2 [mc/h]
AP04
Primary transducer
minimum value
data sheet
transducer
AP05
Primary transducer
maximum value
data sheet
transducer
UP02
Nominal pump current
see motor plate
UP03
Nominal pump frequency
see motor plate
UP05
Operating mode
CF
UP06 Set-point
on demand [mc/h]
9.6. Fixed speed operating mode.
In this mode the system works as a traditional
pump with fixed curve.
9.6.1. Fixed speed operating mode controlled
by keyboard.
Parameters to programm or check (recommended
sequence):
Par.
Description
Suggested value
UP02
Nominal pump current
see motor plate
UP03
Nominal pump frequency
see motor plate
UP05
Operating mode
Man
Man1
Primary fixed speed
operating frequency
on demand [Hz]
To allow which the system works properly,
the operating frequency is limited between
parameter SA03 (minimum operating
frequency) and parameter UP03 (nominal
frequency of the pump).
9.6.2. Fixed speed operation by an external
reference.
If it is necessary to control the frequency from an
external unit it is required to make the connection
as described in section 6.8.
Parameters to programm or check (recommended
sequence):
Par.
Description
Suggested value
UP02
Nominal pump current
see motor plate
UP03
Nominal pump frequency
see motor plate
UP05
Operating mode
Man
AP02
Primary transducer supply
on demand
AP04
Primary transducer minimum
value
0
AP05
Primary transducer maximum
value
100
Man3
Remote control activation
On
Man4
Minimum value for remote
control
on demand [Hz]
The maximum frequency (parameter UP03) will
be related to the maximum value of the external
reference.
I-MAT_Ed6.indd 41
I-MAT_Ed6.indd 41
18/11/20 08:21
18/11/20 08:21
Summary of Contents for I-MAT 11,2 TT-B
Page 2: ...I MAT_Ed6 indd 2 I MAT_Ed6 indd 2 18 11 20 08 20 18 11 20 08 20...
Page 146: ...RU C 146 164 I MAT_Ed6 16 I MAT_Ed6 indd 146 I MAT_Ed6 indd 146 18 11 20 08 21 18 11 20 08 21...
Page 160: ...160 164 I MAT_Ed6 I MAT_Ed6 indd 160 I MAT_Ed6 indd 160 18 11 20 08 22 18 11 20 08 22...
Page 161: ...I MAT_Ed6 161 164 I MAT_Ed6 indd 161 I MAT_Ed6 indd 161 18 11 20 08 22 18 11 20 08 22...
Page 163: ...I MAT_Ed6 indd 163 I MAT_Ed6 indd 163 18 11 20 08 22 18 11 20 08 22...