I-MAT_Ed6 - Operating Instructions
9.7. Night mode
Night mode is an optional operating mode which
reduces the frequency of the system when the
temperature is below a certain value.
This option use a feedback of a temperature
transducer connected as described in section 6.7.
(secondary transducer electrical connection).
Because on I-MAT only two analog inputs
are available, this option does not allow
other options or operating modes which
need 2 transducers (i.e. differential mode).
Parameters to programm or check (recommended
sequence):
Par.
Description
Suggested value
AP06
Secondary transducer supply
data sheet
transducer
AP07
Secondary transducer
measuring unit
4 [°C]
AP08
Secondary transducer
minimum value
data sheet
transducer
AP09
Secondary transducer
maximum value
data sheet
transducer
AP10
Secondary transducer mode
nMOd
AP18
Night mode enable
On
AP19
Night mode activation
on demand [°C]
AP20
Night mode activation time
on demand [s]
AP21
Night mode disable threshold
on demand [°C]
At this point the symbol will appear on the
frequency converter display.
The frequency converter will work at the minimum
operating frequency when the measured
temperature of the transducer goes below the
temperature set in parameter AP19 for the time
set in parameter AP20. The system will return in
normal mode when the temperature will rise above
the threshold value set in parameter AP21.
10. Secondary functions
ON
10.1. Dry-run protection
The frequency converter is equipped with a dry-run
protection for the pumps. When the pressure of the
system remain for a time higher than the dry-run
time (AP22) lower than the value of the dry-run
pressure (AP24) the protection system will stop the
pump.
It is possible to install up to 2 float switches for the
dry-run protection (see section 6.8 for electrical
connection).
Programming primary float switch
The float switch input is default active, parameter
AP40 is set on 2 (nO), parameter AP41 (restart
time) is set on 3s by default.
Through parameter AP41 is possible to set a restart
time from 1 up to 60 seconds.
Programming secondary float switch
The float switch input is default active, parameter
AP42 is set on 2 (nO), parameter AP43 (restart
time) is set on 3s by default.
Through parameter AP43 is possible to set a restart
time from 1 up to 60 seconds.
10.2. Enabling Max/Min curve operation
It’s possible to connect to the frequency converter
an input signal to enable the operation with the
maximum curve or minimum curve. For electrical
connection see section 6.9.
It is possible to enable this operating mode by
changing the parameter AP44 on value 2 “nO” or 3
“nC” (function of the input configuration).
Set parameter AP45 on 1 if it is required which the
frequency converter operates at nominal frequency
(UP03).
Set parameter AP44 on 2 if it is required which
the frequency converter operates at minimum
frequency (SA03).
10.3. Enabling second set-point operation
It is possible to connect to the frequency converter
an input signal in order to use an alternative set-
point. For electrical connection see section 6.10.
It is possible to enable this operating mode by
changing the parameter AP46 on value 2 “nO” or 3
“nC” (function of the input configuration).
If the digital input is enabled the system does not
use the primary set-point (parameter UP06), but it
uses the secondary set-point (parameter UP07).
10.4. Enabling remote On/Off control
It’s possible to connect to the frequency converter
an input signal to start and stop the pump from
a remote unit. For the electrical connection see
section 6.11.
This option is enabled by parameter AP47 on the
value “nO”.
If the digital input is active the frequency converter
is stopped and the display shows “Off”, otherwise
if the digital input is deactivated the frequency
converter will work normally.
10.5. Remote alarm settings
It’s possible to connect to the frequency converter
up to 2 alarm signals. For electrical connection see
section 6.12.
Output signals are default active (parameters AP32
and AP34 set on value “On”).
The parameter AP33 allows to select the activation
condition for the relay connected to terminals A1-
A5.
I-MAT_Ed6.indd 42
I-MAT_Ed6.indd 42
18/11/20 08:21
18/11/20 08:21
Summary of Contents for I-MAT 11,2 TT-B
Page 2: ...I MAT_Ed6 indd 2 I MAT_Ed6 indd 2 18 11 20 08 20 18 11 20 08 20...
Page 146: ...RU C 146 164 I MAT_Ed6 16 I MAT_Ed6 indd 146 I MAT_Ed6 indd 146 18 11 20 08 21 18 11 20 08 21...
Page 160: ...160 164 I MAT_Ed6 I MAT_Ed6 indd 160 I MAT_Ed6 indd 160 18 11 20 08 22 18 11 20 08 22...
Page 161: ...I MAT_Ed6 161 164 I MAT_Ed6 indd 161 I MAT_Ed6 indd 161 18 11 20 08 22 18 11 20 08 22...
Page 163: ...I MAT_Ed6 indd 163 I MAT_Ed6 indd 163 18 11 20 08 22 18 11 20 08 22...