TRIGGER
PRE
POST
ACQUISITION WINDOW
Recorded
Not Recorded
Overlapping Triggers
EVENT n
EVENT n+1
EVENT n+2
Fig. 7.3:
Trigger Overlap
As a trigger is refused, the current buffer is not frozen and the acquisi on con nues wri ng on it. The
EVENT COUNTER can be programmed in order to be either incremented or not. If this func on is enabled,
the EVENT COUNTER value iden fies the trigger number sent (but the event number sequence is lost); if
the func on is not enabled, the EVENT COUNTER value coincides with the sequence of buffers saved and
readout.
UM3247 - N6724 User Manual rev. 10
25