- 10 -

- 11 -

Be sure to keep fireplace dampers closed when not in use . They provide 
an excellent escape route for heat, as well as humidity . 
On occasion, indoor moisture producing activities such as clothes drying, 
cooking, showers, etc ., may raise the humidity level higher than it should 
be, even though the humidifier is not operating . Telltale indications are 
condensation or frost on cold surfaces such as windows, doors, walls, 
etc . If such condensation persists for several hours, your home should be 
ventilated to dissipate the potentially damaging excess moisture .

ADDITIONAL INFORMATION

MAINTENANCE

NOTE:

 The manufacturer of the device recommends that service be 

performed only by a qualified technician . Contact your installing contractor 
for service . See Cautions and Warnings on pages 2 and 3 prior to 
attempting these procedures .

Turn humidifier off and allow humidifier to drain. Disconnect 
power before servicing.

Inspect humidifier at approximately 500 hour intervals or several times 
during the humidification season .
•  Check system operation and inspect all plumbing connections and piping 

for signs of cracks or leaks .

•  Inspect drain line to make sure it is not blocked and has constant 

downward slope . Clean or replace if necessary .

•  Inspect steam hose to make sure it has no low spots and has constant 

upward slope from humidifier to dispersion tube in duct . If dispersion 
tube is mounted below humidifier, inspect drip tee drain .

•  Two canisters are available for optimal performance . The Model 8043RP 

is for typical water while the Model 8043LCRP is designed for low 
conductivity and 120V installations . The 8043LCRP should never be used 
with softened water .

Replace the canister annually and when prompted by the “Service” light .  
Use only genuine replacement part number 8043RP or 8043LCRP .
1 .   Press On/Off switch to turn humidifier off . Humidifier will drain for four 

minutes .

2 .   Allow humidifier to drain . When the green “drain” LED stops flashing, 

disconnect main electrical power to humidifier .

3 .   Remove front panel .
4 .   Pull three wires off posts on top of canister . (Two large electrode 

conductors and one water level probe conductor .)

5 .   Loosen hose clamp at top of canister .
6 .   Slide hose off top of canister .
7 .   Slide canister up and out of drain assembly . Discard canister .
8 .   Remove  O-ring from drain assembly using small screw driver .
9 .   Inspect drain assembly and remove any debris . See drain valve cleaning 

procedure in Installation & Maintenance manual .

10 .   Insert  new  O-ring into slot in drain assembly . (O-ring is provided with 

canister .) Dampen O-ring with water before inserting canister . Do not use 
oil, grease, or any lubricant besides water .

11 .   Make sure strainer is inserted into bottom of new canister .
12 .   Insert canister into drain assembly . Position canister with label facing 

outward .

13 .   Slip steam hose over top of canister and tighten hose clamp .
14 .   Reattach three wires to posts on top of canister . (Larger electrode 

conductors are interchangeable .)

15 .   Replace front panel .
16 .   Inspect drain line to make sure it is not blocked and has constant 

downward slope . Clean or replace if necessary .

17 .   Inspect steam hose to make sure it has no low spots and has constant 

upward slope from humidifier to dispersion tube in duct . If dispersion 
tube is mounted below humidifier, inspect drip tee drain .

18 .   Restore electrical power to humidifier .
19 .   Turn humidifier on and verify green “On/Off” light is illuminated .
20 .   See  Start-up  Procedure in Installation, Operation & Maintenance manual .

TO REPLACE THE CANISTER

TO SERVICE FILL VALVE

If water flow from fill valve is restricted, disconnect inlet fitting and remove 
in-line strainer using small screw from inlet port . Clean or replace strainer . 

Turn the control knob to the maximum RH setting . Make sure that the 
water saddle valve is open and that the humidifier is on . The indoor unit 
blower must be running for the humidifier to function . Once humidifier 
operation is verified, reduce the Humidifier Control setting to the 
recommended inside humidity, depending on the outside temperature . 

CHECK THE HUMIDIFIER OPERATION

Summary of Contents for EHUMD800ASM00BA

Page 1: ...200 Troup Highway Tyler TX 75711 9010 READ AND SAVE THESE INSTRUCTIONS Residential Steam Humidifier Owner s Manual Includes Safety Operating Instructions EHUMD800ASM00BA EHUMD800BSMLCBA Envirowise Steam Humidifier 32 5092 03 ...

Page 2: ...cess panels until electrical power is disconnected Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of the system ELECTRICAL SHOCK HAZARD If the humidifier starts up responding to a call for humidity during maintenance severe bodily injury or death from electrical shock could occur Follow the procedures in this manual before performing se...

Page 3: ...Canister 90 1522 Steam Outlet Drain Supply Water Drain Cup Drain Valve Canister Electrodes High Water Level Sensor Flow Control Orifice Inlet Fill Valve Overflow Fill Fill Cup Thank you for your recent steam humidifier purchase We appreciate your business and are pleased to add your name to our growing list of customers You have invested in the highest quality equipment available Your humidifier w...

Page 4: ... is illuminated green When the canister is being filled or replenished with water the Fill light illuminates green When the canister is being drained the Drain light illuminates green During initial start up with a new canister the humidifier may run through a series of fill drain cycles until the conductivity of the water is in a range that allows normal operation During this time the Steam light...

Page 5: ...rent level below 75 of the maximum operating current Humidifier continues to operate but at reduced capacity Solid Red Operational problem with humidifier Humidifier shuts down Occurs when unit detects over current which can be caused by failure to drain or other system failures Call your heating and air conditioning dealer for service HUMIDIFIER CONTROL OPERATING INSTRUCTIONS The control provided...

Page 6: ... LED stops flashing disconnect main electrical power to humidifier 3 Remove front panel 4 Pull three wires off posts on top of canister Two large electrode conductors and one water level probe conductor 5 Loosen hose clamp at top of canister 6 Slide hose off top of canister 7 Slide canister up and out of drain assembly Discard canister 8 Remove O ring from drain assembly using small screw driver 9...

Page 7: ... showing the proper preventative maintenance All Product parts replaced by Company under this limited warranty must be given to the servicing provider for return to Company Air handlers air conditioners heat pumps cased or uncased coils and stand alone furnaces must be part of an Air Conditioning Heating and Refrigeration Institute rated and matched system or a specification in a Company provided ...

Page 8: ...nger twenty 20 years TABLE 1 continued FURNACES First digit may be a T or an A UD1 DD1 UD1 H DD1 H UD2 DD2 UE1 DE1 Base Limited Warranty Period Parts five 5 years Heat Exchanger twenty 20 years Registered Limited Warranty Period Parts ten 10 years Heat Exchanger twenty 20 years S9V2 S9X2 UC1 DC1 UD2 V DD2 V UD2 C V DD2 C V UH1 DH1 UX1 DX1 UH2 DH2 UHM DHM Base Limited Warranty Period Parts five 5 y...

Page 9: ...to original owner purchase date and install location will be required including a service diagnosis of failure The purchaser is responsible for all costs of warranty service including but not limited to any related service labor or diagnosis calls The purchaser relinquishes all rights to ownership of the returned unit SPECIFIC TERMS FOR COMMERCIAL APPLICATIONS Base Limited Warranty Period Applies ...

Page 10: ...s five 5 years GW 658 4217 FC GW 658 4217 CONDITIONS SPÉCIFIQUES POUR LES UNITÉS TRIPHASÉES Modèles allant jusqu à 5 tonnes destinés aux bâtiments RÉSIDENTIELS UNITÉS EXTÉRIEURES TRIPHASÉES 2TTA 4TTA 4TWA 4A7C 4A6C UNITÉS MONOBLOCS TRIPHASÉES 4TCY4 4TCX3 4TCC3 4WCZ6 4DCZ6 4WCY4 4DCY4 4WCX3 4WCC3 4YCZ6 4YCY4 4YCX3 4YCC3 Période de validité de base de la garantie limitée Serpentin extérieur pièces d...

Page 11: ...ice de garantie notamment mais non exclusivement tout service de main d œuvre ou appel de diagnostic L acheteur renonce à tout droit de propriété sur l unité renvoyée CONDITIONS SPÉCIFIQUES POUR LES APPLICATIONS COMMERCIALES La durée de garantie limitée de base s applique pour tous les systèmes de régulation produits de zonification humidificateurs déshumidificateurs et ventilateurs à récupération...

Page 12: ...ur douze 12 ans serpentins pièces de remplacement dix 10 ans échangeur de chaleur vingt 20 ans TABLEAU 1 suite CHAUDIÈRES À AIR CHAUD la première lettre peut être un T ou un A UD1 DD1 UD1 H DD1 H UD2 DD2 UE1 DE1 Période de validité de base de la garantie limitée Pièces de remplacement cinq 5 ans échangeur de chaleur vingt 20 ans Période de validité de la garantie limitée pour les produits enregist...

Page 13: ...ertu de la présente garantie limitée doivent être remises au prestataire de service pour être retournées à la Société Les centrales de traitement d air climatiseurs pompes à chaleur serpentins en boîtier ou sans boîtier et chaudières à mazout doivent faire partie d un système reconnu par l ACHRI Institut de climatisation chauffage et refroidissement ou d une spécification apparaissant dans un bull...

Page 14: ... sur la partie supérieure de la cartouche Deux gros conducteurs d électrode et un conducteur de capteur de niveau d eau 5 Desserrez la bride de serrage située sur le dessus de la cartouche 6 Glissez le boyau du dessus de la cartouche 7 Glissez la cartouche vers le haut et hors de l assemblage d évacuation Jetez la cartouche 8 R etirez le joint torique de l assemblage d évacuation au moyen d un pet...

Page 15: ...iveau actuel inférieur à 75 du courant de fonctionnement maximal L humidificateur continue de fonctionner mais à capacité réduite Rouge continu Problème de fonctionnement avec l humidificateur L humidificateur s éteint Se produit lorsque l unité détecte une surintensité qui peut être causée par une défaillance d évacuation ou d autres défaillances du système Appelez votre concessionnaire de chauff...

Page 16: ...he le voyant On Off marche arrêt s allume en vert Lorsque la cartouche est remplie ou ravitaillée en eau le voyant Fill remplissage s allume en vert Lorsque la cartouche se vide le voyant Drain évacuation s allume en vert Durant la mise en marche initiale avec une nouvelle cartouche l humidificateur peut passer à travers une série de cycles de remplissage d évacuation jusqu à ce que la conductivit...

Page 17: ...ouche 90 1522 Sortie de vapeur Évacuation Eau d alimentation Godet d évacuation Robinet de vidange Cartouche Électrodes Capteur de niveau élevé d eau Orifice de contrôle du débit Robinet de remplissage d admission Débordement Remplissage Godet de remplissage Merci d avoir acheté un humidificateur à vapeur Nous vous remercions d avoir fait cet achat et nous sommes heureux d ajouter votre nom à notr...

Page 18: ...branchée Respectez la procédure d arrêt indiquée dans ce manuel avant d effectuer toute procédure de service ou d entretien sur toute pièce du système DANGER DE CHOC ÉLECTRIQUE Si l humidificateur se met en marche en réponse à une demande d humidité pendant une procédure d entretien des blessures graves ou mortelles peuvent survenir à la suite d un choc électrique Respectez les procédures décrites...

Page 19: ...1 9010 LIRE ET CONSERVER CES DIRECTIVES Humidificateur à vapeur résidentiel Guide d utilisation Comprend les directives de sécurité et de fonctionnement EHUMD800ASM00BA EHUMD800BSMLCBA Envirowise humidificateur à vapeur 32 5092 03 10012948 B2207982A 7 18 ...

Reviews: