OPERATING MODES

Your Steam Humidifier can be installed to operate on 120 volts, 208 volts 
or 240 volts using 11 .5 or 16 .0 amps . The higher the voltage and amperage 
the higher the potential output .

Amperage

Voltage

Maximum steam capacity (gal/day)

11 .5

120V

11 .5

208V

20 .5

240V

23 .3

16 .0

120V

16 .0

208V

30 .0

240V

34 .6

It may take several days for the humidifier to reach rated capacity 
depending on the input voltage and the electrical conductivity of 
the water. 

120 volt systems take longer to reach rated capacity than 240 

volt systems . The humidifier should always be plumbed to cold water but 
the water can be softened or unsoftened . The water supply should have a 
conductivity between 125 and 1,250 uS/cm which correlates loosely to a 
hardness between 3 and 36 grains/gallon . The humidifier will make steam 
when plumbed to low-conductivity water but will take longer to reach 
nominal capacity . There are benefits and trade-offs to consider when both 
hard and softened water are available .

Hard water:

 The benefit of hard water is less frequent draining and filling 

than with soft water, which results in better energy and water efficiency 
and more consistent steam output . However, canister replacement could 
be more frequent with hard water because mineral deposits coat the 
electrodes . The harder the water, the more frequent the need for a new 
canister .

Softened water:

 The benefit of softened water is typically longer 

canister life than with hard water because softened water does not coat 
the electrodes nearly as much as hard water . However, softened water 
ions stay in solution to much higher concentrations than hard water ions . 
This requires more frequent draining and filling which results in lower 
efficiency, higher water consumption and less consistent steam output .
Two canisters are available, the Model 8043RP and Model 8043LCRP, 
optimized for different water types . Contact your HVAC dealer for canister 
selection .

INSTALLATION OPTIONS & EFFECT OF  

WATER CHARACTERISTICS

When the humidifier is powered and turned on, the “On/Off” light is 
illuminated green .
When the canister is being filled or replenished with water, the “Fill” light 
illuminates green .
When the canister is being drained, the “Drain” light illuminates green .
During initial start up with a new canister, the humidifier may run through 
a series of fill/drain cycles until the conductivity of the water is in a range 
that allows normal operation . During this time, the “Steam” light illuminates 
green . If the humidifier cannot produce steam at the rated level after trying 
for 168 hours, the “Steam” light illuminates yellow . The humidifier continues 
to operate in this state until the rated output is reached .
The conductivity of naturally soft water, hard water, and softened water 
changes as the water heats up, but the internal controller adjusts the 
water level to maintain a nominal current between the electrodes . Over 
the life of the canister, minerals that build up on the electrodes will reduce 
their effective surface area and affect the resistance between them . The 
operating water level will increase with use until it reaches the high water 
level probe . At that point, the “Service” light will flash red indicating that 
the canister needs to be replaced . The humidifier will continue to operate 
but with reduced output .
When the humidifier begins a drain cycle, the fill valve opens to introduce 
cold water into the canister . This is done to prevent hot water from 
entering the drain . The drain valve remains open for four minutes to allow 
all water to drain from the canister . 
Any time power is disconnected or humidifier is turned off, the internal 
timer for start-up and drain cycles is reset .
If the humidifier has operated 168 hours without a drain cycle, the drain 
valve will open and drain the canister . Normal operation will continue .
If the humidifier is operating and a power failure occurs, once power 
is restored, the “On/Off” light will flash green for one minute, then the 
humidifier will turn on .

END OF SEASON/PERIOD OF INACTIVITY SHUT-DOWN

If the humidifier does not receive a call to operate in 72 hours, the 
humidifier controller drains the canister . The “Drain” light will remain on 
until there is a humidity call or 24 hours has elapsed . The humidifier will 
resume normal operation when a call for humidity is made .

Summary of Contents for EHUMD800ASM00BA

Page 1: ...200 Troup Highway Tyler TX 75711 9010 READ AND SAVE THESE INSTRUCTIONS Residential Steam Humidifier Owner s Manual Includes Safety Operating Instructions EHUMD800ASM00BA EHUMD800BSMLCBA Envirowise Steam Humidifier 32 5092 03 ...

Page 2: ...cess panels until electrical power is disconnected Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of the system ELECTRICAL SHOCK HAZARD If the humidifier starts up responding to a call for humidity during maintenance severe bodily injury or death from electrical shock could occur Follow the procedures in this manual before performing se...

Page 3: ...Canister 90 1522 Steam Outlet Drain Supply Water Drain Cup Drain Valve Canister Electrodes High Water Level Sensor Flow Control Orifice Inlet Fill Valve Overflow Fill Fill Cup Thank you for your recent steam humidifier purchase We appreciate your business and are pleased to add your name to our growing list of customers You have invested in the highest quality equipment available Your humidifier w...

Page 4: ... is illuminated green When the canister is being filled or replenished with water the Fill light illuminates green When the canister is being drained the Drain light illuminates green During initial start up with a new canister the humidifier may run through a series of fill drain cycles until the conductivity of the water is in a range that allows normal operation During this time the Steam light...

Page 5: ...rent level below 75 of the maximum operating current Humidifier continues to operate but at reduced capacity Solid Red Operational problem with humidifier Humidifier shuts down Occurs when unit detects over current which can be caused by failure to drain or other system failures Call your heating and air conditioning dealer for service HUMIDIFIER CONTROL OPERATING INSTRUCTIONS The control provided...

Page 6: ... LED stops flashing disconnect main electrical power to humidifier 3 Remove front panel 4 Pull three wires off posts on top of canister Two large electrode conductors and one water level probe conductor 5 Loosen hose clamp at top of canister 6 Slide hose off top of canister 7 Slide canister up and out of drain assembly Discard canister 8 Remove O ring from drain assembly using small screw driver 9...

Page 7: ... showing the proper preventative maintenance All Product parts replaced by Company under this limited warranty must be given to the servicing provider for return to Company Air handlers air conditioners heat pumps cased or uncased coils and stand alone furnaces must be part of an Air Conditioning Heating and Refrigeration Institute rated and matched system or a specification in a Company provided ...

Page 8: ...nger twenty 20 years TABLE 1 continued FURNACES First digit may be a T or an A UD1 DD1 UD1 H DD1 H UD2 DD2 UE1 DE1 Base Limited Warranty Period Parts five 5 years Heat Exchanger twenty 20 years Registered Limited Warranty Period Parts ten 10 years Heat Exchanger twenty 20 years S9V2 S9X2 UC1 DC1 UD2 V DD2 V UD2 C V DD2 C V UH1 DH1 UX1 DX1 UH2 DH2 UHM DHM Base Limited Warranty Period Parts five 5 y...

Page 9: ...to original owner purchase date and install location will be required including a service diagnosis of failure The purchaser is responsible for all costs of warranty service including but not limited to any related service labor or diagnosis calls The purchaser relinquishes all rights to ownership of the returned unit SPECIFIC TERMS FOR COMMERCIAL APPLICATIONS Base Limited Warranty Period Applies ...

Page 10: ...s five 5 years GW 658 4217 FC GW 658 4217 CONDITIONS SPÉCIFIQUES POUR LES UNITÉS TRIPHASÉES Modèles allant jusqu à 5 tonnes destinés aux bâtiments RÉSIDENTIELS UNITÉS EXTÉRIEURES TRIPHASÉES 2TTA 4TTA 4TWA 4A7C 4A6C UNITÉS MONOBLOCS TRIPHASÉES 4TCY4 4TCX3 4TCC3 4WCZ6 4DCZ6 4WCY4 4DCY4 4WCX3 4WCC3 4YCZ6 4YCY4 4YCX3 4YCC3 Période de validité de base de la garantie limitée Serpentin extérieur pièces d...

Page 11: ...ice de garantie notamment mais non exclusivement tout service de main d œuvre ou appel de diagnostic L acheteur renonce à tout droit de propriété sur l unité renvoyée CONDITIONS SPÉCIFIQUES POUR LES APPLICATIONS COMMERCIALES La durée de garantie limitée de base s applique pour tous les systèmes de régulation produits de zonification humidificateurs déshumidificateurs et ventilateurs à récupération...

Page 12: ...ur douze 12 ans serpentins pièces de remplacement dix 10 ans échangeur de chaleur vingt 20 ans TABLEAU 1 suite CHAUDIÈRES À AIR CHAUD la première lettre peut être un T ou un A UD1 DD1 UD1 H DD1 H UD2 DD2 UE1 DE1 Période de validité de base de la garantie limitée Pièces de remplacement cinq 5 ans échangeur de chaleur vingt 20 ans Période de validité de la garantie limitée pour les produits enregist...

Page 13: ...ertu de la présente garantie limitée doivent être remises au prestataire de service pour être retournées à la Société Les centrales de traitement d air climatiseurs pompes à chaleur serpentins en boîtier ou sans boîtier et chaudières à mazout doivent faire partie d un système reconnu par l ACHRI Institut de climatisation chauffage et refroidissement ou d une spécification apparaissant dans un bull...

Page 14: ... sur la partie supérieure de la cartouche Deux gros conducteurs d électrode et un conducteur de capteur de niveau d eau 5 Desserrez la bride de serrage située sur le dessus de la cartouche 6 Glissez le boyau du dessus de la cartouche 7 Glissez la cartouche vers le haut et hors de l assemblage d évacuation Jetez la cartouche 8 R etirez le joint torique de l assemblage d évacuation au moyen d un pet...

Page 15: ...iveau actuel inférieur à 75 du courant de fonctionnement maximal L humidificateur continue de fonctionner mais à capacité réduite Rouge continu Problème de fonctionnement avec l humidificateur L humidificateur s éteint Se produit lorsque l unité détecte une surintensité qui peut être causée par une défaillance d évacuation ou d autres défaillances du système Appelez votre concessionnaire de chauff...

Page 16: ...he le voyant On Off marche arrêt s allume en vert Lorsque la cartouche est remplie ou ravitaillée en eau le voyant Fill remplissage s allume en vert Lorsque la cartouche se vide le voyant Drain évacuation s allume en vert Durant la mise en marche initiale avec une nouvelle cartouche l humidificateur peut passer à travers une série de cycles de remplissage d évacuation jusqu à ce que la conductivit...

Page 17: ...ouche 90 1522 Sortie de vapeur Évacuation Eau d alimentation Godet d évacuation Robinet de vidange Cartouche Électrodes Capteur de niveau élevé d eau Orifice de contrôle du débit Robinet de remplissage d admission Débordement Remplissage Godet de remplissage Merci d avoir acheté un humidificateur à vapeur Nous vous remercions d avoir fait cet achat et nous sommes heureux d ajouter votre nom à notr...

Page 18: ...branchée Respectez la procédure d arrêt indiquée dans ce manuel avant d effectuer toute procédure de service ou d entretien sur toute pièce du système DANGER DE CHOC ÉLECTRIQUE Si l humidificateur se met en marche en réponse à une demande d humidité pendant une procédure d entretien des blessures graves ou mortelles peuvent survenir à la suite d un choc électrique Respectez les procédures décrites...

Page 19: ...1 9010 LIRE ET CONSERVER CES DIRECTIVES Humidificateur à vapeur résidentiel Guide d utilisation Comprend les directives de sécurité et de fonctionnement EHUMD800ASM00BA EHUMD800BSMLCBA Envirowise humidificateur à vapeur 32 5092 03 10012948 B2207982A 7 18 ...

Reviews: