Description of application and parameters
Constant light switch application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
83
11.4
Constant light switch application
11.4.1 General parameters — Output is of type
Options:
1 bit
1 byte 0 - 100%
1 byte 0 - 255
Light scene number (1-64)
RTC operating mode switchover (1 byte)
2-byte float
– 1 Bit: Intended for switch actuators.
– 1 Byte 0 - 100%: For activating dimmers.
– 1 Byte 0 - 255: For actuators, which are activated with a value of between 0 and 255.
– Light scene number 1 - 64: For activating light scenes.
– RTC operating mode switchover (1 Byte): To directly switch room temperature controllers
into a specific operating mode.
– Auto
– Comfort
– Standby
– ECO
– Frost/heat
protection
– 2-byte float: To send a specific temperature for example.
Note
If the type of output is changed, also the options for setting the parameters
change.
– Value for switch-on at output 1
– Value for switch-off at output 1
and when they are activated also for:
– Value for switch-on at output 2
– Value for switch-off at output 2
In this manual only values for the 1-bit setting are described.
11.4.2 General parameters — Cyclic sending of value for switch-on
Options:
No
Yes
– No: The setpoint is sent only once via the bus.
– Yes: The setpoint is sent cyclic via the bus.
– Parameter "cyclic repeat time" is also displayed.