Description of application and parameters
"Detector" application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
66
11.3.4 General parameters — Output object sends at
Options:
Switch-on / switch-off
Switch-on
Switch-off
– Switch-on/switch-off: Sends a telegram at the start of movement and at the end of switch-off
delay.
– Switch-on: Only sends a telegram at the start of movement.
– Switch-off: Only sends a telegram at the end of switch-off delay.
Note
If switch-on or switch-off has been selected, the following parameters are not
displayed:
– Value for switch-on
– Cyclic sending of value for switch-on
– Value for switch-off
– Cyclic sending of value for switch-off
11.3.5 General parameters — Value for switch-on
Options:
On
Off
– On: When the detector detects movement, value 1 is sent via the bus.
– Off: When the detector detects movement, value 0 is sent via the bus.
11.3.6 General parameters — Cyclic sending of value for switch-on
Options:
No
Yes
– No: The setpoint is sent only once via the bus.
– Yes: The setpoint is sent cyclic via the bus.
– Parameter "cyclic repeat time" is also displayed.