Description of application and parameters
"Detector" application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
70
11.3.16 Extended parameter settings — Use of a two-stage switch-off
Note
This parameter is only displayed when "Output is of type" is set on 1 byte 0 -
100% or 1 byte 0 - 255.
Options:
No
Yes
– No: The detector has a switch-off delay and, following the switch-off delay, transmits what
has been set under the "Value for switch-off" parameter.
– Yes: After the switch-off delay the detector first switches to the set reduced brightness and
only then sends the value set under the "Value for switch-off" parameter after brightness
reduced according to switch-off delay.
Example: Switch-off delay = 5 minutes
– Value for switch-off = 0%
– Value for reduced brightness = 20%
– Brightness reduced according to switch-off delay = 3 minutes
If movement is now no longer detected, the light is dimmed to 20% after 5 minutes and then to
0% after a further 3 minutes (switch-off).
11.3.17 Extended parameter settings — Value for reduced brightness (%)
Options:
0 .. 20 .. 100
– Here the value for the reduced brightness is set. After the switch-off delay has expired the
detector is to dim the light to this value.
11.3.18 Extended parameter settings — Brightness reduced according to switch-off delay
(hh:mm:ss)
Options:
00:00:10 .. 00:05:00 .. 18:12:15
– Here the value for the switch-off delay of the reduced brightness is set. The total switch-off
delay then consists of the switch-off delay + brightness reduced according to switch-off
delay.