Description of application and parameters
Communication objects — Object RTC
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
182
11.19.6 Actual temperature
Number
Name
Object function
Data type
6
1. Actual temperature
Output
2-byte floating point
value
2. Actual temperature weighted
2-byte floating point
value
1. The object outputs the measured (room) temperature, adjusted by the calibration value.
2. The object outputs the temperature value which is calculated from the recording and
weighting of internal and up to two external temperatures.
Note
An external temperature measurement for room control may be practical for
larger rooms and/or floor heating.
11.19.7 External actual temperature
Number
Name
Object function
Data type
7
External actual temperature
Input
2-byte floating point
value
2-byte communication object for reading an external temperature value provided via the KNX
bus.
11.19.8 External actual temperature 2
Number
Name
Object function
Data type
8
External actual temperature 2
Input
2-byte floating point
value
2-byte communication object for reading an additional external temperature value provided via
the KNX bus.