Description of application and parameters
Application "RTC object"
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
152
11.8.101 Temperature reading — Monitoring time for temperature reading (0 = no monitoring)
(min)
Options:
Setting option between 1 - 120
If no temperature is read within the parameterised time period, the device switches to error
mode. It transmits a telegram to the bus via the "Actual temperature error" object and applies
the operating mode and control value for error settings.
11.8.102 Temperature reading — Operating mode for fault
Options:
Cool
Heat
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently specify the heating/cooling operating type. As a result, the operating type
best suited to protecting the building will be selected.
Note
This parameter is only available when the "Control function" parameter is set to
"Heating and cooling" or "Heating and cooling with additional stage".
11.8.103 Temperature reading — Control value for fault (0 - 255)
Options:
Setting option between 1 - 255
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently determine the control value. Therefore, a control value which is suitable
for protecting the building will be selected.