59
Figure 9a: Recommended MPC Minimum Piping - Single Boiler Application
NOTES:
1. All piping is schedule 40.
2. Pipe sizes listed are based on a 20°F
or 40°F Delta T (temperature rise
across the boiler).
Select one to match application.
3. When specified supply/return piping
size is less than 4”, install appropriate
size reducer directly onto boiler supply
and return manifolds.
4. Drain valve - ball valve preferable,
gate valve acceptable alternative
(supplied by others). Minimum valve
size per ASME Code is 3/4” NPT.
5. Swing joints may be piped over the top
of the boiler if space is limited.
6. System design must accommodate the
above Boiler Operating Requirements.
7. Diaphragm expansion tank shown, but
other types of air elimination systems
may be used.
Boiler
Model
Supply / Return
20°F Rise
40°F Rise
Nom. I.D.
(Inch)
Water Side
Press. Drop
(Ft/Wtr)
Flow
Rate
(GPM)
Nom. I.D.
(Inch)
Water Side
Press. Drop
(Ft/Wtr)
Flow
Rate
(GPM)
MPC4
2
1.9
42.4
1½
0.9
21.2
MPC5
2
2.6
65.2
1½
1.6
32.6
MPC6
2
3.3
83.7
1½
2.3
41.9
MPC7
2½
4.0
102.3
1½
3.0
51.2
MPC8
2½
4.7
120.9
2
3.7
60.5
MPC9
3
5.4
139.6
2
4.4
69.8
MPC10
3
6.1
158.1
2
5.1
79.0
MPC11
3
6.8
176.7
2
5.8
88.3
MPC12
3
7.5
195.2
2½
6.4
97.6
MPC13
4
8.2
213.8
2½
7.1
106.9
MPC14
4
8.9
232.3
2½
7.8
116.1
MPC15
4
9.6
250.9
2½
8.5
125.5
MPC16
4
10.3
269.5
3
9.2
134.8
MPC17
4
11.0
288.1
3
9.9
144.1
MPC18
4
11.7
306.6
3
10.6
153.3
1
Boiler Operating Requirements:
• Minimum Return Water Temperature = 80°f
• Maximum Delta T = 80°f
• Minimum supply Water Temperature = 130°f
Summary of Contents for MPC
Page 19: ...19 Figure 5 Manual or Hydraulic Draw up Section Assembly ...
Page 28: ...28 Table VII Modular Return Water Mixing Tube RWMT RC ...
Page 29: ...29 Figure 13 Return Water Mixing Tube RC Assembly and Installation ...
Page 78: ...78 Figure 56 MPC Common Bare Boiler Components ...
Page 80: ...80 Figure 56 MPC Common Bare Boiler Components continued ...
Page 82: ...82 Figure 57 MPC Front Center Section Frame Rail Assembly ...
Page 84: ...84 Figure 58 MPC Rear Section Frame Rail Assembly ...
Page 86: ...86 Figure 59 MPC Return Water Mixing Tube RC Assembly ...
Page 88: ...88 Figure 60 MPC Heat Exchanger Insulation Wrapper ...
Page 90: ...90 Figure 61 MPC Internal Wiring Harness Components ...
Page 92: ...92 Figure 62 MPC Jacket Panel Assembly ...
Page 94: ...94 Figure 62 MPC Jacket Panel Assembly continued ...
Page 96: ...96 Figure 63 MPC 2 nd and 3 rd Pass Flueway Baffles ...