8640 - 55
PROFIBUS-DP
HI
Main battery on the PROFIBUS-DP
Example: Hl: DIP-6 main battery DIP switch 6
EIn
Extension battery n on the RIO bus (n = 0 bis 7 )
Example: El0: DIP-4 extension battery with Address = Switch 4
DIP-n
DIP switch number of the corresponding valve battery
(at the right on the field bus module) 0:= OFF; 1:=ON
24 V Out
The 24V output control voltage is missing on the corresponding valve battery
0:=No fault; 1:=fault
NOK
The corresponding extension battery does not log on at the RIO bus
0:=No fault; 1:=fault
Konfig
The corresponding extension battery was configured by the Master
0:=Not configured; 1:=configured
Configuration and Parametrisation faults
Configuration fault number
Parametrisation fault number
1
Too many inputs (>32) for one battery
1
Too many inputs (>32) entered for one battery
2
Too many outputs (>24) for one battery
2
Too many outputs (>24) entered for one battery
3
Too few inputs for all batteries
(default from parameter telegram)
3
Parametrising telegram too small
4
Too few outputs for all batteries
(default from parameter telegram)
4
Too few outputs for all batteries
5
False configuration byte
5
Summary of Contents for 8640
Page 10: ...8 8640 GENERAL INSTRUCTIONS ...
Page 22: ...20 8640 MODULES FOR CONVENTIONAL CONNECTION TECHNICS ...
Page 58: ...56 8640 PROFIBUS DP ...
Page 98: ...96 8640 FIELD BUS MODULE INTERBUS S ...
Page 118: ...116 8640 SELECAN ...
Page 152: ...150 8640 AS INTERFACE ...
Page 156: ...154 8640 INPUT EXPANSION MODULE FOR TRANSDUCERS ...
Page 178: ...176 8640 INTERNAL BUS EXTENSION ...
Page 189: ......
Page 194: ......
Page 195: ......
Page 196: ...The smart choice of Fluid Control Systems www buerkert com ...