36 - 8640
PROFIBUS-DP
Manual configuration
If no GSD file is available, manual configuration must be performed. The following data apply. A
configuration telegramme may contain one or more identifiers, allowing the user to allocate them freely.
The identifiers are built up as follows:
Physically present
Configuration
Effect
16 valves
1 Byte
Only valves 1 to 8 may be communicated to
2 Byte
Valves 1 to 16 may be communicated to
3 Byte
Valves 1 to 16 may be communicated to,
1byte in the process map is occupied but unused
4 Byte
Configuragtion error
Bit 7
Bit 6
Bit 5 - 4
Bit 3 - 0
Consistency
0 = Byte/Word
1 = entire length
Bytes/Words
0 = Bytes
1 = Words (2 Byte)
Input/Output
00 = special identifier format
01 = input
10 = output
11 = input/output
Lenght (number) of data
0000 = 1 Byte/Word
:
0010 = 3 Bytes/Words
:
1111 = 16 Bytes/Words
Hex
Decimal
Meaning
10
016
1 Byte input, consistency via Byte
11
017
2 Byte input, consistency via Byte
12
018
3 Byte input, consistency via Byte
13
019
4 Byte input, consistency via Bytee
20
032
1 Byte output, consistency via Byte
21
033
2 Byte output, consistency via Byte
22
034
3 Byte output, consistency via Byte
00
000
Reserve (blank))
Summary of Contents for 8640
Page 10: ...8 8640 GENERAL INSTRUCTIONS ...
Page 22: ...20 8640 MODULES FOR CONVENTIONAL CONNECTION TECHNICS ...
Page 58: ...56 8640 PROFIBUS DP ...
Page 98: ...96 8640 FIELD BUS MODULE INTERBUS S ...
Page 118: ...116 8640 SELECAN ...
Page 152: ...150 8640 AS INTERFACE ...
Page 156: ...154 8640 INPUT EXPANSION MODULE FOR TRANSDUCERS ...
Page 178: ...176 8640 INTERNAL BUS EXTENSION ...
Page 189: ......
Page 194: ......
Page 195: ......
Page 196: ...The smart choice of Fluid Control Systems www buerkert com ...