8640 - 25
PROFIBUS-DP
Setting the DIP switches
Using the DIP switches, you can carry out settings for the field bus module. It is located on the right-
hand side, in the lower part of the bus module (see also General view Field bus technology PROFIBUS-
DP). In order to access the DIP switch, remove the plugged-in termination module.NOTEA change of the
switch position only becomes active after the field bus module has been restarted.
NOTE
A change of the switch position only becomes active after the field bus module has been
restarted.
Address of the PROFIBUS-DP subscribers: DIP switches 1 to 7
Each subscriber on the PROFIBUS has a unique address. This address is set at the valve battery using
DIP switches 1 to 7.
RIO interface: DIP Switch 8
You can connect extension batteries using the internal bus (RIO). If the internal bus is used, DIP switch 8
must be set to ON. The RIO interface module is inserted onto the PROFIBUS-DP field bus module (see
Chapter Electrical Base Module Output).
DIP-1 DIP-2 DIP-3 DIP-4
DIP-5 DIP-6 DIP-7
Adress
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0
ON
OFF
OFF
OFF
OFF
OFF
OFF
1
OFF
ON
OFF
OFF
OFF
OFF
OFF
2
ON
ON
OFF
OFF
OFF
OFF
OFF
3
OFF
OFF
ON
ON
ON
ON
ON
124
ON
OFF
ON
ON
ON
ON
ON
125
1
2
3
4
5
6
7
8
9
10
11
12
Adress of the PROFIBUS-DP-
subscriber 0-125
RIO-Interface
ON: active
Input
mode
Input filter
ON: active
Profibus
address via
the bus
Summary of Contents for 8640
Page 10: ...8 8640 GENERAL INSTRUCTIONS ...
Page 22: ...20 8640 MODULES FOR CONVENTIONAL CONNECTION TECHNICS ...
Page 58: ...56 8640 PROFIBUS DP ...
Page 98: ...96 8640 FIELD BUS MODULE INTERBUS S ...
Page 118: ...116 8640 SELECAN ...
Page 152: ...150 8640 AS INTERFACE ...
Page 156: ...154 8640 INPUT EXPANSION MODULE FOR TRANSDUCERS ...
Page 178: ...176 8640 INTERNAL BUS EXTENSION ...
Page 189: ......
Page 194: ......
Page 195: ......
Page 196: ...The smart choice of Fluid Control Systems www buerkert com ...