Page 15
SERVICE (cont.)
BYPASS VALVE
Location:
The bypass valve is located inside the right front
of the hood.
Test Procedures:
1. Disconnect the brewer from the power source.
Place a server beneath the brewing funnel.
2. Check the water level in the tank to confirm that it
is within 1/2" from the top of the tank.
3. Connect the brewer to the power source.
4. Check the bypass valve for coil action. Place the
ON/OFF switch in the "ON" position, press and
release the BREW switch. Listen carefully in the
vicinity of the bypass valve for a "clicking" sound as
the coil magnet attracts and repels the plunger.
5. Disconnect the brewer from the power source.
If the sound is heard as described, there may be a
blockage in the bypass valve or the water line to the
sprayhead. Remove the bypass valve and inspect for
wear, and remove waterborne particles.
If the sound is not heard as described, proceed to #6.
6. Connect the voltmeter lead ends to the dispense
valve coil terminals. Connect the brewer to the
power source. With the selector switch in the 1.5
or 1.75 gallon position, place "ON/OFF" Switch in
the "ON" position. Press and release the brew
switch. The indication must be:
P774
FIG. 2 BYPASS VALVE
FIG.3 BYPASS VALVE TERMINALS
22978.0000
TL5
TL4
TL3
TL2
TL1
J2
J1
SE
T
LO
CK
LOCK
SET
1 2 3 4 5 6
P2230
WHI/GRN to Dispence Valve
WHI/VIO to Brew Selector Switch
28230 031201
a.) 120 volts ac for two wire 120 volt models, 208
volts ac for three wire 120/208 volt models and
240 volts ac for three wire 120/240 volt models.
b.) 200 to 240 volts ac for two wire 200 or 240 volt
models.
7. Disconnect the brewer from the power source.
If voltage is present as described, but no coil action is
observed, nor "clicking" heard, bypass valve is defec-
tive. Replace valve and test again to verify repair.
If voltage is not present as described, refer to
Wiring
Diagrams and check the brewer wiring harness. Also
check the control board for proper operation. See
Pages 23 through 27.
Removal and Replacement:
1. Remove the wires from the bypass valve.
2. Drain enough water from the tank so bypass valve
is above the water level.
3. Remove water lines from valve.
4. Remove two nuts retaining bypass valve inside the
hood and remove bypass valve.
5. Remove hose barb fitting and attach to new by-
pass valve.
6. Install new bypass valve with hose barb fitting.
7. Reconnect the water tubes and the wires to the
bypass valve.
8. Refer to Fig. 3 when reconnecting the wires.