7
Heating system inspection and maintenance
Logano GE615 - We reserve the right to make any changes due to technical modifications.
48
Cleaning brushes (optional extra)
Using the cleaning brushes ensures optimum cleaning of
the boiler.
The various brush types available are shown in
Æ
Fig. 64.
For brush dimensions and where to use the brushes,
please see
Æ
Tab. 1.
Fig 64 Cleaning brushes
z
Clean the upper and lower hot gas flues with cleaning
brushes 4 and 5.
z
Clean the combustion chamber with cleaning brush 8.
V
Remove the combustion residues by sweeping them
forwards through the combustion chamber opening
and through the clean-out openings on the rear section
and the flue gas header
Æ
Fig. 63, page 47.
z
Check packing cords on the clean-out openings and
burner door. Replace damaged or hardened packing
cords.
Fig 65 Cleaning the hot gas flues
1
Lower hot gas flues
2
Combustion chamber
3
Upper hot gas flues
No. of
sections
Brush ID
Brush dimensions
(diameter in mm)
Used in
Shaft designation
K = adapter
Längen der
Stangen in mm
9 - 11
4
5
8
75x110
60x73
200x80
Secondary heating surface
Secondary heating surface
Combustion chamber
A + K
2000
12 -14
4
5
8
75x110
60x73
200x80
Secondary heating surface
Secondary heating surface
Combustion chamber
A + K
2500
15 -16
4
5
8
75x110
60x73
200x80
Secondary heating surface
Secondary heating surface
Combustion chamber
A + G + K
2000 + 1000
Tab. 14 Brush dimensions and brush application locations
Packing cords are available from your nearest
branch.
Summary of Contents for Logano GE615
Page 60: ......