2
Product Information
Logano GE615 - We reserve the right to make any changes due to technical modifications.
6
Specifications and dimensions
Water capacity
l
561
621
681
741
801
861
921
981
Gas content
l
922
1027
1132
1237
1342
1447
1552
1657
Flue gas
temperature1)
partial load 60 %
°C
140
Flue gas
temperature1) full
load
°C
170 – 180
Flue gas mass flow
rate, oil, partial load
60 %
°C
0,1537
0,1778
0,1995
0,2207
0,2479
0,2750
0,2992
0,3234
Flue gas mass flow
rate, oil, full load2)
kg/s
0,2320
–
0,2615
0,2592
–
0,3028
0,3001
–
0,3396
0,3364
–
0,3763
0,3727
–
0,4222
0,4181
–
0,4678
0,4635
–
0,5093
0,5043
–
0,5505
Flue gas mass flow
rate, gas, partial
load 60%
kg/s
0,1542
0,1785
0,2002
0,2215
0,2488
0,2760
0,3003
0,3246
Flue gas mass flow
rate, gas, full load2)
kg/s
0,2328
–
0,2625
0,2602
–
0,3039
0,3012
–
0,3408
0,3376
–
0,3776
0,3741
–
0,4237
0,4196
–
0,4694
0,4652
–
0,5112
0,5061
–
0,5525
CO2 content, oil
%
13
CO2 content, gas
%
10
Required draught
Pa
0
Hot gas resistance
mbar
2,4
3,4
4,2
4,2
4,1
4,5
5,4
5,8
Permissible flow
temperature3)
°C
110
4)
100
– 120
5)
Permissible
operating pressure
bar
6
Maximum time
constant T on
thermostat
s
40
Maximum time
constant T on
monitor/limiter
s
40
Tab. 2
Specifications and dimensions
1)
To DIN EN 303. The minimum flue gas temperature for the chimney calculation acc. to DIN 4704 is approx.
12 K lower.
2)
Full load details relate to the upper and lower rated output range.
3)
Safety limit (high limit safety cut-out). Max. possible flow temperature = safety limit (STB) – 18 K.
Example: Safety limit (STB) = 100 °C, max. possible flow temperature = 100 – 18 = 82 °C.
4)
Permitted flow temperature for Switzerland.
5)
According to country-specific standards and regulations (for all countries)
Summary of Contents for Logano GE615