C
−
LRV lift control valve
Operation
300−I−9010212−E−10/08.08
Setting "Relevelling"
S
Operative during fine adjustment
S
Higher value: faster travel speed
S
Setting range:
0.20–1.50V
S
Standard:
0.40V
Important
: low settings for "Relevelling" may cause slow travel to be
uneven due to static friction in the cylinder and car guides
Important
: low settings for "Relevelling" and "Soft−Stop" may cause
slight variations in levelling accuracy.
Setting "P sol. static"
S
Operative in steady−state control processes (constant−speed travel)
S
Higher value: higher solenoid control gain
S
Setting range:
0.20–1.50
S
Standard:
UP
0.80
DOWN
0.70
Important
: high settings may cause oscillations.
Setting "I sol. static"
S
Operative in steady−state control processes (constant−speed travel)
S
Higher value: longer solenoid reset time
S
Setting range:
100–1000ms
S
Standard:
UP
900ms
DOWN
700ms
Important
: low settings may cause oscillations.
Setting "D sol."
S
Higher value: longer solenoid derivative time
S
Setting range:
0–100ms
S
Standard:
20ms
S
To disable, set to:
0ms
Important
: high settings may cause oscillations.