LRV lift control valve
Operation
300−I−9010212−E−10/08.08
Setting "SIU−1 difference"
S
Demand/feedback difference − only operative when SIU−1 is activated
S
Setting range:
20–50% of fast travel speed
S
Standard:
25%
Setting "SIU−4 threshold"
S
Feedback threshold − only operative when SIU−4 is activated
S
Setting range:
2.0–5.0V
S
Standard:
2.5V
Determining the SIU−4 threshold:
Car speed Fast UP
x
= ... [Volt]
Speed in door zone
Dem. value Fast UP
Setting "Accel. inspection"
S
Only operative with inspection speed (K5)
S
Higher value: greater acceleration, i.e. shorter acceleration distance
S
Setting range:
0.30–5.00V/s
S
Standard:
2.00V/s
Setting "Inspection speed"
S
K5 gives inspection speed
S
Higher value: faster travel speed
S
Setting range:
20–80% of fast travel speed
S
Standard:
50%
Important
: only operative with fast travel speed
Setting "Decel. inspection"
S
Only operative with inspection speed (K5)
S
Higher value: greater deceleration, i.e. shorter deceleration distance
S
Setting range:
0.30–10.00V/s
S
Standard:
4.00V/s