LRV lift control valve
Product description
300−I−9010212−E−10/08.08
S
By using relays K6, K7 or K8, various reductions in the nominal
speed can be achieved (e.g. for different floor spacings)
S
The speed reduction can be adjusted between 20–100% of nominal
speed
S
Speed can be set by means of parameter "K6 speed" (or "K7 speed" /
"K8 speed") in the Options menu to match the floor spacing (distance
between stops)
S
Acceleration can be adjusted separately via parameters "K6 acceler-
ation" (or "K7 acceleration" / "K8 acceleration") in the Options menu
S
Deceleration can be adjusted separately via parameters "K6 deceler-
ation" (or "K7 deceleration" / "K8 deceleration") in the Options menu