LRV lift control valve
Operation
300−I−9010212−E−10/08.08
Setting "P sol. dynamic"
S
Operative in dynamic control processes (acceleration, deceleration)
S
Higher value: higher solenoid control gain
S
Setting range:
0.20–1.50
S
Standard:
UP 0.80
DOWN
0.70
Important
: high settings may cause oscillations.
Setting "I sol. dynamic"
S
Operative in dynamic control processes (acceleration, deceleration)
S
Higher value: longer solenoid reset time, greater control error in
dynamic processes
S
Setting range:
100–1000ms
S
Standard:
UP
450ms
DOWN
350ms
Important
: low settings may cause oscillations.
Setting "Calibr. factor"
S
Valve calibration (feedback)
S
Setting range:
0.90 − 1.30
S
Standard:
1.00