C
−
LRV lift control valve
Operation
300−I−9010212−E−10/08.08
Setting "Fast speed"
S
Higher value: faster travel speed
S
Setting range:
1.00–10.00V
S
Standard:
7.00V
S
Example of litres <=> volts conversion,
⇒
Setting "Deceleration"
S
Higher value: greater deceleration, i.e. shorter deceleration distance
S
Setting range:
0.30–5.00V/s
S
Standard:
3.00V/s
Setting "Slow speed"
S
Operative after fast travel
S
Higher value: faster travel speed
S
Setting range:
0.20–2.50V
S
Standard:
0.40V
Important
: low settings for "Slow speed" may cause slow travel to be
uneven due to static friction in the cylinder and car guides
Important
: low settings for "Slow speed" and "Soft−Stop" may cause
slight variations in levelling accuracy.
Setting "Soft−Stop"
S
Higher value: greater deceleration, i.e. shorter stopping distance,
harsher stopping jolt
S
Setting range:
0.20–5.00V/s
S
Standard:
1.00V/s
S
To disable
:
set to 5.00V/s
Important
: low settings for "Slow speed" and "Soft−Stop" may cause
slight variations in levelling accuracy.