C
−
LRV lift control valve
Operation
300−I−9010212−E−10/08.08
Setting "K6/K7/K8 acceleration"
S
Only operative with auxiliary speeds (K6, K7, K8)
S
Higher value: greater acceleration, i.e. shorter acceleration distance
S
Setting range:
0.30–5.00V/s
S
Standard K6:
0.80V/s
S
Standard K7:
1.20V/s
S
Standard K8:
1.60V/s
Setting "K6/K7/K8 speed"
S
Fast speed is reduced with K6, K7, K8
S
Higher value: faster travel speed
S
Setting range:
20–100% of fast speed
S
Standard K6:
20%
S
Standard K7:
30%
S
Standard K8:
40%
Important
: only operative with fast travel speed
Setting "K6/K7/K8 deceleration"
S
Only operative with auxiliary speeds (K6, K7, K8)
S
Higher value: greater deceleration, i.e. shorter deceleration distance
S
Setting range:
0.30–5.00V/s
S
Standard K6:
1.20V/s
S
Standard K7:
1.80V/s
S
Standard K8:
2.40V/s
Setting "Decel. emergency"
S
Only operative for emergency stop (reasons for emergency stop:
activation of SIU−1, timeout error, fault)
S
Higher value: greater deceleration, i.e. shorter deceleration distance
S
Setting range:
5.00–10.00V/s
S
Standard:
10.00V/s
Setting "Pulsation sol."
S
Higher value: higher solenoid pulse frequency (dither)
S
Setting range:
120–220Hz
S
Standard:
220Hz