Commissioning
Once the unit is registered with the Redcare ESP, perform the following steps:
1. Ensure the unit is connected to the network.
2. Power cycle the unit to begin the commissioning process (both headers off).
3. After 1 minute the unit will begin establishing its communication paths.
4. After a further 1 minute, LEDs 2 & 3 should be permanently lit to show that the Wireline &
Wireless paths are both available. Note that the rightmost LED (Power indicator) is LED 1.
Time
hh:mm:ss
Path
Indicator
Pin
CID
(zone)
SIA
(zone)
Description
10:00:00
0x13
1023;0 R350
(999)
NR
(999)
Wireline Path communications restore
10:00:03 0x13 or 23 984;1
E305
(995)
AT
(995)
Unit restarted (power up cycle) event
10:00:04 0x13 or 23 984;3
R305
(995)
AR
(995)
Unit restarted (power up cycle) restore
10:00:11
0x23
1022;0 R350
(998)
NR
(998)
Wireless Path communications restore
Figure 16 – Typical ARC alarm log for Redcare Secure unit initial commission
Note that the unit sends a “Unit Restart” alarm / Restore cycle over the first available
interface if the power to the unit has been interrupted.
(0x13 indicates Wireline path, 0x23 indicates Wireless path).
Test alarms can now be generated.
If the unit is configured for BSIA 175 working, briefly apply an alarm condition to pin input 11. Within
1 minute a pin 988 event & restore should be received at the ARC over both paths. This test proves
that both paths are signalling correctly. Note that if both paths are not available, no alarm will be
received by the ARC.
Time
hh:mm:ss
Path
Indicator
Pin
CID
(zone)
SIA
(zone)
Description
10:05:00
0x13
988;1
E354
(997)
TX
(999)
BSIA 175 IP Test message event (IP)
10:05:02
0x23
988;1
E354
(997)
TX
(998)
BSIA 175 GPRS Test message event
(GPRS)
10:05:02
0x13
988;3
R354
(997)
TE
(999)
BSIA 175 IP Test message restore (IP)
10:05:03
0x23
988;3
R354
(997)
TE
(998)
BSIA 175 GPRS Test message restore
(GPRS)
Figure 17 - Typical ARC alarm log for Redcare Secure unit BSIA Form 175 path test