Page 15 of 40
Installation, Maintenance and Operation Manual V24a (June 2012)
British Telecommunications plc 2012
Configuring Panel Format
By default the unit is configured for pin-only mode. This mode
disables the dial capture port to
reduce power consumption. Use the following command to enable the dial capture port and set it to
receive the relevant panel format where dial capture is required. Note Pins can still be reported in
any of these other modes.
To change the panel format, use the * 15 * option:
* 15 * 1 # ContactID
* 15 * 10 # High Speed (fast format)
* 15 * 20 # SIA
* 15 * 30 # Pin Only mode -
default
The Redcare Secure unit supports several other less common formats listed below:
* 15 * 2 # ContactID with Double Knock
* 15 * 3 # 4 + 1 express (DTMF mode only)
* 15 * 5 # 4 + 2 express (DTMF mode only)
* 15 * 11 # High Speed with Double Knock
* 15 * 21 # SIA with V21 tones
If no more parameters are to be configured, remove the header from J903 and disconnect the DTMF
phone.
Configuring General Purpose Outputs
By default, the Redcare Secure unit’s General Purpose Outputs (GPOP’s) operate as follows:
Output Default Function
Default Polarity
GPOP1 Local path fail output
High to indicate either path
failure. (BSIA 175 mode)
GPOP2 Remotely (ARC) Controlled
0 from ARC sets output High, 1
from ARC sets output Low
GPOP3 RPS function (in conjunction with input pin 4)
Alarm sent sets output High,
Alarm ack’d sets output Low
Figure 11 - General Purpose Output Pin operations