Page 14 of 40
Installation, Maintenance and Operation Manual V24a (June 2012)
British Telecommunications plc 2012
6 |
Configuring the Redcare Secure unit
The unit is supplied pre-configured for pin only input mode and PSTN working. (Secure 2 /
Secure 3)
For most installations no further configuration will be required
.
For alternative installation requirements the following configuration options are available.
There are two methods available to configure the unit. It can be configured with either a DTMF
phone
or
through a web console on a PC internet browser.
Configuration Method 1. Configuring with a DTMF Phone
1. Prepare wiring as described in Section
0
.
2. For initial power-up and configuration, the following minimum connections are required:
a. DC Power
b. Antenna (for wireless operation)
3 Connect a DTMF phone to the units’s alarm panel port J1000. An adapter is available from
Redcare. See fig 10
4 Short out the Config header J903 with a link.
5 Power up or power-cycle the unit
.
6 Around 15 seconds after power on, the six rightmost LED’s will flash providing a period of 20
seconds to lift the telephone receiver, receive dial tone and press the '#' key to enter
configuration Mode.
Note: Configuration Mode is terminated after five minutes, or when the installer hangs-up the
DTMF phone.
Note: If the Config header is left shorted once configuration mode is completed the unit will
not dialup or communicate at all.
Figure 10 – Adapter to connect a DTMF telephone to J1000 for configuration.