24
larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice
at the thermostat.
C
W2
G
W1
R
Y1
Typical
Thermostat
Corrections
O/B/Y2
(see Note)
Note: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2. Do not configure for O output.
Field Wiring
Central
Terminal
Board
W1
Y2
Y1
R
W2
G
C
X
W1
Y2
Y1
R
W2
G
C
X
T–STAT
See
Caution
UNIT DAMAGE HAZARD
Failure to follow this caution may cause a short circuit.
CAUTION
!
Carefully check the connection of control coductor
for indoor fan control at terminal G. Connecting the
indoor fan lead to terminal C will cause a short circuit
condition which can cause component damage inside
the unit or at thermostat.
C14067
Fig. 27 -- Typical Low--Voltage Control Connections
Central Terminal Board
The Central Terminal Board (CTB) is a pass through
connection point. The CTB provides the capability to add
factory--installed options and field--installed accessories to
the units by cutting jumper wires without having to change
or reroute wires through the structure of the unit. The CTB
does not provide any microprocessor control; it is simply a
basic multifunction wiring terminal configuration.
Commercial Defrost Control
The
Commercial
Defrost
Control
Board
(DFB)
coordinates thermostat demands for supply fan control, 1
or 2 stage cooling, 2 stage heating, emergency heating and
defrost control with unit operating sequences. The DFB
also provides an indoor fan off delay feature (user
selectable). See Fig. 28 for board arrangement.
DIP
Switches
Speed-Up
Jumpers
C09275
Fig. 28 -- Defrost Control Board Arrangement
The DFB is located in the 548J unit’s main control box (see
Fig. 29 on page 25). All connections are factory--made
through harnesses to the unit’s CTB, to IFC (belt--drive
motor) or to ECM (direct--drive motor), reversing valve
solenoids and to defrost thermostats. Refer to Table 5 (on
page 25) for details of DFB Inputs and Outputs.
Reversing valve control —
The DFB has two outputs for
unit reversing valve control. Operation of the reversing
valves is based on internal logic; this application does not
use an “O” or “B” signal to determine reversing valve
position. Reversing valves are energized during the
cooling stages and the defrost cycle and de--energized
during heating cycles. Once energized at the start of a
cooling stage, the reversing valve will remain energized
until the next heating cycle demand is received. Once
de--energized at the start of a Heating cycle, the reversing
valves will remain de--energized until the next cooling
stage is initiated.
Summary of Contents for 548J*17 D Series
Page 4: ...4 a548J 015 Fig 2 Unit Dimensional Drawing Size 17 Units ...
Page 5: ...5 a548J 016 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 6: ...6 a548J 017 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 7: ...7 a548J 018 Fig 3 Unit Dimensional Drawing Size 24 Units ...
Page 8: ...8 a548J 019 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 9: ...9 a548J 020 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 13: ...13 C10139 Fig 7 Roof Curb Details Size 17 Units ...
Page 14: ...14 C10140 Fig 8 Roof Curb Details Size 24 Units ...
Page 19: ...19 a50 9696 Fig 20 548J 17 24 Control Wiring Diagram with VFD Option ...
Page 20: ...20 a50 9697 Fig 21 Typical 548J 17 24 Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Page 44: ...44 a50 9699 Fig 44 RTU Open System Control Wiring Diagram ...