41
TEMPERATURE
ENT
HALPY
RA
TEMP
ABSOLUTE HUMIDITY
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ES5
ES4
ES3
ES2
ES1
HL
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P2 (T,RH)
P1
(T,RH)
RA
H
UM
(%
RH
)
a50--- 9997
Fig. 41 -- Single Enthalpy Curve and Boundaries
Table 21 – Single Enthalpy and Dual Enthalpy High Limit Curves (EN Units)
Enthalpy
Curve
Temp.
Dry---Bulb (
_
F)
Temp.
Dewpoint (
_
F)
Enthalpy
(btu/lb/da)
Point P1
Point P2
Temp. (
_
F)
Humidity %RH
Temp. (
_
F)
Humidity %RH
ES1
80.0
60.0
28.0
80.0
36.8
66.3
80.1
ES2
75.0
57.0
26.0
75.0
39.6
63.3
80.0
ES3
70.0
54.0
24.0
70.0
42.3
59.7
81.4
ES4
65.0
51.0
22.0
65.0
44.8
55.7
84.2
ES5
60.0
48.0
20.0
60.0
46.9
51.3
88.5
HL
86.0
66.0
32.4
86.0
38.9
72.4
80.3
The W (heating mode) is not controlled by the W7220 but
it requires the status to know where to position the OA
damper for minimum position for the fan speed.
The 2 speed fan delay is available when the system is
programmed for 2 speed fan (in the System Setup menu
item). The 2 speed fan delay is defaulted to 5 minutes and
can be changed in the Advanced Setup menu item. When
the unit has a call for Y1 In and in the free cooling mode
and there is a call for Y2 In, the 2--speed fan delay starts
and the OA damper will modulate 100% open, the supply
fan should be set to high speed by the unit controller.
After the delay one of two actions will happen:
S
The Y2 In call will be satisfied with the damper 100%
open and fan on high speed and the call will turn off
OR
S
If the call for additional cooling in the space has not
been satisfied then the first stage of mechanical cooling
will be enabled through Y1 Out or Y2 Out.
Checkout
Inspect all wiring connections at the economizer module’s
terminals, and verify compliance with the installation
wiring diagrams.
For checkout, review the Status of each configured
parameter and perform the Checkout tests.
NOTE
:
See “Interface Overview” on page 30 for
information about menu navigation and use of the keypad.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury, death or property damage.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lock(s) and lockout tag(s). Unit may have more
than one power switch. Ensure electrical service to
rooftop unit agrees with voltage an amperage listed on
the unit rating plate.
If any wiring changes are required, first be sure to
remove power from the economizer module before
starting work. Pay particular attention to verifying the
power connection (24 Vac).
!
WARNING
Power Up —
After the W7220 module is mounted and wired, apply
power.
Initial Menu Display —
On initial start up,
Honeywell
displays on the first line
and
Economizer W7220
on the second line. After a brief
pause, the revision of the software appears on the first line
and the second line will be blank.
Summary of Contents for 548J*17 D Series
Page 4: ...4 a548J 015 Fig 2 Unit Dimensional Drawing Size 17 Units ...
Page 5: ...5 a548J 016 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 6: ...6 a548J 017 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 7: ...7 a548J 018 Fig 3 Unit Dimensional Drawing Size 24 Units ...
Page 8: ...8 a548J 019 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 9: ...9 a548J 020 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 13: ...13 C10139 Fig 7 Roof Curb Details Size 17 Units ...
Page 14: ...14 C10140 Fig 8 Roof Curb Details Size 24 Units ...
Page 19: ...19 a50 9696 Fig 20 548J 17 24 Control Wiring Diagram with VFD Option ...
Page 20: ...20 a50 9697 Fig 21 Typical 548J 17 24 Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Page 44: ...44 a50 9699 Fig 44 RTU Open System Control Wiring Diagram ...