34
Table 11 -- Menu Structure* (cont)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED PARAMETER NAME
Notes
SYSTEM
SETUP
INSTALL
01/01/10
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG
_
F
_
F or
_
C
Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT
CONV
Conventional or HP
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input from
thermostat or controller.
See Menu Note 4
AUX2 IN
n/a
Shutdown (SD)
Heat (W1)
HP (O)
HP (B)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2---speed fan mode, you must program CONV mode
for W. Shutdown is not available in 2---speed fan mode.
See Menu Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN SPEED
1speed
1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan.
The controller does not control the fan but positions the OA and RA
dampers to the heating or cooling mode. See page 35 for modes and
position.
NOTE: 2---speed fan option also needs Heat (W1) programmed in
AUX 2 In. See Menu Note 4.
FAN CFM
5000cfm
100 to 15000 cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter ONLY if using DCVCAL ENA = AUTO
The value is found the nameplate label for the specific RTU.
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
ERV = Energy Recovery Ventilator
[[
EXH2 = second damper position 24 Vac out for second exhaust fan
SYS = use output as an alarm signal
OCC
INPUT
INPUT or ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 Vac), the 24 Vac
is input “INPUT” to the OCC terminal. If no occupancy output from the
thermostat then change program to “ALWAYS” OR add a jumper from
terminal R to OCC terminal.
See Menu Note 1.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD will briefly
flash YES and change to NO but all parameters will change to the factory
default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2---speed
values.
ADVANCED
SETUP
MA LO SET
45
_
F
(7
_
C)
35 to 65
_
F;
(2 to 18
_
C)
Incremented by 1
_
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to activate Freeze Protection (close damper and alarm if
temperature falls below setup value)
FREEZE POS
CLO
CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CLO = closed
MIN = MIN POS or VENTMAX
CO2 ZERO
0ppm
0 to 500 ppm:
Increment by 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN
2000ppm
1000 to 3000 ppm;
Increment by 50
CO
2
ppm span to match CO
2
sensor. e.g.; 500---1500 sensor output would
be 500 CO
2
zero and 1000 CO
2
span.
STG3 DLY
2.0h
0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 h or OFF
COOLING STAGE 3 DELAY
Delay after stage 2 for cool has been active. Turns on second stage of
mechanical cooling when economizer is first stage call and mechanical
cooling is second stage call. Allows three stages of cooling, 1
economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS
CLO
CLO or OPN
Indicates shutdown signal from space thermostat or unitary controller.
When controller receives 24 Vac input on the SD terminal in conventional
mode, the OA damper will open if programmed for OPN and OA damper
will close if programmed for CLO. All other controls, e.g., Y1---O, Y2---O,
EXH1, etc. will shut off.
NOTE: Function NOT AVAILABLE with 2---speed mode
DA LO ALM
45
_
F
(7
_
C)
NONE
35 to 65
_
F; (2 to 18
_
C)
Incremented by 5
_
Used for alarm for when the DA air temperature is too low. Set lower range
of alarm, below this temperature the alarm will show on the display.
DA HI ALM
80
_
F
(27
_
C)
NONE
70 to 180
_
F; (21 to 82
_
C)
Incremented by 5
_
Used for alarm for when the DA air temperature is too high. Set high range
of alarm, above this temperature the alarm will show on the display
DCVCAL ENA
MAN
MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA and MA sensor conditions. Requires all sensors (RA,
OA, MA and CO
2
).
NOTE: This operation is not operable with a 2---speed fan unit.
Summary of Contents for 548J*17 D Series
Page 4: ...4 a548J 015 Fig 2 Unit Dimensional Drawing Size 17 Units ...
Page 5: ...5 a548J 016 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 6: ...6 a548J 017 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 7: ...7 a548J 018 Fig 3 Unit Dimensional Drawing Size 24 Units ...
Page 8: ...8 a548J 019 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 9: ...9 a548J 020 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 13: ...13 C10139 Fig 7 Roof Curb Details Size 17 Units ...
Page 14: ...14 C10140 Fig 8 Roof Curb Details Size 24 Units ...
Page 19: ...19 a50 9696 Fig 20 548J 17 24 Control Wiring Diagram with VFD Option ...
Page 20: ...20 a50 9697 Fig 21 Typical 548J 17 24 Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Page 44: ...44 a50 9699 Fig 44 RTU Open System Control Wiring Diagram ...