50
SW3 Protocol Selection
PROTOCOL
DS8
DS7
DS6
DS5
DS4
DS3
DS2
DS1
BACnet MS/TP
(Master)
Unused
OFF
OFF
OFF
ON
OFF
Select Baud Select Baud
Modbus
(Slave)
Unused
OFF
OFF
ON
ON
OFF
Select Baud Select Baud
N2
(Slave)
Unused
OFF
OFF
OFF
ON
ON
OFF
OFF
LonWorks
Unused
ON
ON
OFF
ON
OFF
OFF
ON
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE
DS2
DS1
9600
OFF
OFF
19,200
ON
OFF
38,400
OFF
ON
76,800
ON
ON
C07166
Fig. 57 -- RTU Open SW3 Dip Switch Settings
C10815
Fig. 58 -- RTU Open Address Switches
C10816
Fig. 59 -- Network Wiring
Local Access
Wall Mounted Equipment Touch
t
Interface:
The
Equipment Touch interface is a wall mounted interface used
to connect to the RTU Open controller to access the control
information, read sensor values, and perform maintenance.
This is an accessory interface that does not come with the
RTU Open controller. Wire the Equipment Touch interface
to the RTU Open controller J13 local access port. There are
2 password protected levels in the display (User and Admin).
See the Equipment Touch Installation and Setup Guide for
more information. See Appendix A in the guide for
navigation and screen content.
Field Assistant:
Field Assistant is a computer program
included with the purchase of the Tech Tool Kit
(USB-TKIT). This is a field Tech Tool to set-up, service, or
download application software to the RTU Open controller
and includes a USB Link Cable. The link cable connects a
USB port to the J12 local access port. See Fig. 60.
RTU Open Troubleshooting —
Communication LEDs:
The LEDs indicate if the
controller is speaking to the devices on the network. The
LEDs should reflect communication traffic based on the
baud rate set. The higher the baud rate the more solid the
LEDs will appear. See Table 23.
NOTE
: Refer to the RTU Open Multi--Protocol Controller
Controls, Start--Up, Operation and Troubleshooting manual.
Contact your Bryant applications engineer for details on
configuration and troubleshooting of connected networks.
Summary of Contents for 548J*17 D Series
Page 4: ...4 a548J 015 Fig 2 Unit Dimensional Drawing Size 17 Units ...
Page 5: ...5 a548J 016 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 6: ...6 a548J 017 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Page 7: ...7 a548J 018 Fig 3 Unit Dimensional Drawing Size 24 Units ...
Page 8: ...8 a548J 019 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 9: ...9 a548J 020 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Page 13: ...13 C10139 Fig 7 Roof Curb Details Size 17 Units ...
Page 14: ...14 C10140 Fig 8 Roof Curb Details Size 24 Units ...
Page 19: ...19 a50 9696 Fig 20 548J 17 24 Control Wiring Diagram with VFD Option ...
Page 20: ...20 a50 9697 Fig 21 Typical 548J 17 24 Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Page 44: ...44 a50 9699 Fig 44 RTU Open System Control Wiring Diagram ...