background image

39

Installation

NOTE

: Design and install the air distribution system to comply

with Air Conditioning Contractors of America manuals and/or
NFPA pamphlets 90A and 90B or other approved methods that
conform to local codes and good trade practices.

1. When furnace supply ducts carry air outside furnace area,

seal return air duct to furnace casing and terminate duct

outside furnace space.

2. Install air conditioning cooling coil (evaporator) on outlet

side of furnace.

3. For furnaces installed without a cooling coil it is recom-

mended that the outlet duct be provided with a removable

access panel. This panel should be accessible when the

furnace is installed so the exterior of the heat exchanger

can be viewed for inspections. The access panel

MUST

be

sealed to prevent leaks.

4. If separate evaporator and blower units are used, install

good sealing dampers for air flow control. Chilled air go-

ing through the furnace could cause condensation and

shorten the furnace life.

NOTE

: Dampers (field supplied) can be either automatic or

manual. Manually operated dampers

MUST

be equipped with a

means to prevent furnace or air conditioning operation unless
damper is in the full heat or cool position.

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or

death.
Cool air passing over heat exchanger can cause condensate to

form resulting in heat exchanger failure.

!

WARNING

Connections

NOTE

: On upflow installations, return air can enter through

either side, both sides, or the bottom. On horizontal installations
the return air must enter through the knockout opening in the
lower panel of the furnace. Return air

can not

enter through rear

of the furnace. When the furnace is located in an area near or
adjacent to the living area, the system should be carefully
designed with returns to minimize noise transmission through the
return grille. Any blower moving a high volume of air will
produce audible noise which could be objectionable to when the
unit is located very close to living areas. It is advisable to route
the return air ducts under the floor or through the attic.

1. For side connections using a 16

x 25

(406 x 635 mm)

filter, cut out the embossed area shown in Fig. 41. This

will provide a 14

1

/

2

x 22

1

/

2

(368 x 572 mm) approxim-

ate opening.

NOTE

:

Furnaces with 5 ton cooling rating may require both

(left and right) side return or one side and bottom return.
Side return air duct(s) is not permitted with horizontal
furnace installation.

Embossed Area
on Side of Furnace

A = 14 /

2

(368.3mm) Height of Cutout for 16

x 25

(406.4 x 635mm) Filter

B = 22

1

/

2

(571.5mm) Width of Cutout for 16

x 25

(406.4 x 635mm) Filter

A

Furnace
Bottom

B

A07728

Fig. 41 -- Side Return Air Cutout

2. Bottom returns can be made by removing the knockout

panel in the furnace base. Do

NOT

remove knock-out ex-

cept for a bottom return.

3. Installation of locking-type dampers are recommended in

all branches, or in individual ducts to balance system’s air

flow.

4. Non-combustible, flexible duct connectors are recommen-

ded for return and supply connections to furnace.

5. If air return grille is located close to the fan inlet, install at

least one, 90

°

air turn between fan and inlet grille to re-

duce noise.

NOTE

: To further reduce noise, install acoustical air turning

vanes and/or line the inside of duct with acoustical material.

Sizing

Existing or new ductwork

MUST

be sized to handle the correct

amount of airflow for either heating only or heating and air

conditioning.

Insulation

1. Insulate ductwork installed in attics or other areas exposed

to outside temperatures with a minimum of 2

(51 mm)

insulation and vapor barrier.

2. Insulate ductwork in indoor unconditioned areas with a

minimum of 1

(25 mm) insulation with indoor type vapor

barrier.

Filters

A Filter

must

be used:

Filters are not supplied with these furnaces, but can be purchased

from the distributor.
Use either filter type:

S

Washable, high velocity filters are based on a maximum

air flow rating of 600 FPM.

S

Disposable, low velocity filters are based on a maxim-

um air flow of 300 FPM when used with filter grille.

S

See

Circulating Air Blower Data

for additional data.

NOTE

: Disposable, low velocity filters may be replaced with

washable, high velocity filter providing they meet the minimum
size areas. Washable, high velocity filters can be replaced

ONLY

with same type and size.

359AA

V

Summary of Contents for 4-WAY MULTIPOISE 359AAV

Page 1: ...sulted before installation to determine the need to obtain a permit IPEX System 636 is a trademark of IPEX Inc CONSIGNES SP CIALES POUR L IN STALLATION DE VENTILLATION AU CANADA L installation faite a...

Page 2: ...or of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 3: ...h unit and other safety precautions that may apply These instructions cover the minimum requirements and conform to existing national standards and safety codes In some instances these instructions ex...

Page 4: ...ldings or structures under construction S This furnace is NOT approved for installation in mobile homes trailers or recreation vehicles S Seal around supply and return air ducts S Install correct filt...

Page 5: ...to the plastic Transition box Squeeze the hose together near the end and quickly reconnect the 3 4 19 mm OD rubber hose to the stub on the condensate trap Secure with the hose clamp When you return ho...

Page 6: ...the floor S Located or physically protected from possible damage by a vehicle 10 Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in atti...

Page 7: ...For venting information literature contact www Bryant com with the complete model and serial number of the furnace On the Dual Certified furnace the vent and combustion air pipes attach to the furnace...

Page 8: ...2 122 2 27 318 177 5 609 6 30 2 249 2 177 8 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723 9 57 2 336 6 60 3 27 1016 19 1 587 4 98 4 Specifications are subj...

Page 9: ...t or masonry chimney Multistory venting is NOT permitted If this furnace is replacing a previously common vented furnace it may be necessary to resize the existing vent and chimney to prevent oversizi...

Page 10: ...322 cm2 33 3 sq in 215 cm2 25 sq in 161 cm2 6 152 mm EXAMPLE Determining Free Area Furnace 100 000 Furnace 100 000 Water Heater 30 000 Water Heater 30 000 Total Input 130 000 4 000 Total Input 130 000...

Page 11: ...idered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in 2 1 000 BTUH 4 400 mm2 kW of total input rating of al...

Page 12: ...ce can NOT be common vented or connected to any type B BW or L vent or vent connector nor to any portion of a factory built or masonry chimney If this furnace is replacing a previously common vented f...

Page 13: ...12 The minimum pipe run length is 2 6 M 13 The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing It can also be run in the same chase with a ven...

Page 14: ...are required the length can be INCREASED by 5 1 5 M for each additional elbow NOT used NOTE It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters t...

Page 15: ...15 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW A06675 Fig 7 Direct Vent Termination Clearance 359AAV...

Page 16: ...16 Fig 8 Other than Direct Vent Termination Clearance 359AAV...

Page 17: ...remain in the furnace between the door switch plate and the blower shelf Fig 9 during operation See Fig 19 for proper routing and installation of the overflow DO NOT trap the drain line in any other l...

Page 18: ...rommet in loose parts bag S Install the 1 2 13 mm CPVC street elbow on discharge of trap S Install the black PVC tube connector 3 4 18 mm PVC x 1 2 13 mm CPVC from loose parts bag as shown in the illu...

Page 19: ...of 2 51 mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 51 mm PVC tee or A 2 PVC coupling fastened onto the drain tee S Install tee trap in...

Page 20: ...the vent drain to the trap Secure all connections with clamps S Install the vent pipe grommet into the casing S Cut an appropriate length of 2 51 mm PVC pipe long enough to exit the cabinet and conne...

Page 21: ...to the left side of the unit using the two 2 screws provided Cut the 5 8 16 mm ID corrugated hose as shown above and fasten the 90 bend end to the trap and fasten the straight end to the transition dr...

Page 22: ...o the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Connect the corrugated drain tube from the transition box to the trap as shown If an e...

Page 23: ...he 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the trap Secure connections with clamps S Rem...

Page 24: ...e will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrug...

Page 25: ...Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from...

Page 26: ...will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugat...

Page 27: ...ig 18 that corresponds to the installation position of the furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe jo...

Page 28: ...til it bottoms out NOTE Cement MUST be fluid while inserting pipe If NOT recoat pipe 4 Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fittin...

Page 29: ...ng materials may be affected by flue products expelled in close proximity to unprotected surfaces Sealing or shielding of the exposed surfaces with a corrosion resistant material such as aluminum shee...

Page 30: ...Snow Level 36 Min 2 50 8mm Max 36 Min OR 914 4mm 914 4mm A07718 Fig 25 Concentric Vent and Combustion Air Roof Termination A Vent Dimension A is touching or 2 in 503 8mm maximum separation 25 22 02d...

Page 31: ...he installation from Table 4 and Fig 32 2 Determine the best location for the termination kit See Fig 31 for vertical termination or Fig 35 for horizontal termination Roof termination is preferred sin...

Page 32: ...Airflow restriction will occur and the furnace pressure switch may cause intermittent operation Drill clearance hole in rain cap and pilot hole in vent pipe Stainless steel screw Field supplied A07722...

Page 33: ...essures Combustion Air Vent Combustion Air Vent 45 Elbow Field Supplied 25 22 02 Strap Field Supplied Flush to 1 25 4mm max Note Securing strap must be field installed to prevent movement of termina t...

Page 34: ...in National Fuel Gas Code or CGA codes 3 Two stage regulation of Propane gas is recommended Propane Conversion FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or d...

Page 35: ...2 pressure switches Manual shut off valve Alternative installation Representative drawing only some models may vary in appearance A07724 Fig 36 Typical Gas Piping for Upflow Use elbows and 3 76 mm pip...

Page 36: ...s 6 and 7 Table 7 LPG or Propane Gas Manifold Pressure in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL Ft M 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000...

Page 37: ...injury and or loss of life WARNING 1 The furnace and the equipment shut off valve must be dis connected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 38: ...e 115V HUM called HUM on Control is energized when the inducer is energized ELECTRONIC AIR CLEANER EAC is energized when there is a blower speed call except is NOT energized when blower operates in th...

Page 39: ...ucts under the floor or through the attic 1 For side connections using a 16 x 25 406 x 635 mm filter cut out the embossed area shown in Fig 41 This will provide a 141 2 x 221 2 368 x 572 mm approxim a...

Page 40: ...unit to avoid condensation on the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the furnace This allows for installation in the horizontal right or...

Page 41: ...tent 1 Turn OFF gas supply to all appliances and start furnace Use jumper wire on R to W for Heat 2 Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution Re...

Page 42: ...inal will not be available at the Unused Motor Lead location Continuous Fan Operation using G Energizing the G terminal on the furnace control provides continuous fan operation This is done by connect...

Page 43: ...lve is energized the main burners light and flame is sensed S The igniter is de energized after the main burners ignite S FCB will delay blower operation for the 30 seconds timed from the opening of t...

Page 44: ...ger than two minutes 1 hr delay roll out switch requires manual reset 8 Flashes Permanent Lockout Gas valve relay contact stuck closed or miswired gas valve power reset only 10 Flashes Line voltage 11...

Reviews: