Bryant 4-WAY MULTIPOISE 359AAV Installation Instructions Manual Download Page 42

42

will lower the temperature rise. A lower blower speed will

increase the temperature rise.

Changing Blower Speed

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
Turn OFF power to furnace before changing speed taps.

!

WARNING

NOTE

: The speed taps that the manufacturer sets from the

factory for this product are based on a nominal 400 CFM per ton
cooling and the basic mid range on the temperature rise for
heating.

Since the manufacturer cannot establish the static pressure

that will be applied to the unit, it is the responsibility of the

installer dealer/contractor to select the proper speed taps for

the application when the unit is installed.

If it is necessary to change speeds, refer to steps below.

REDUCED FURNACE LIFE HAZARD

Failure to follow this caution may result in reduced furnace

life.
Use ONLY the blower motor speed taps insert indicated in

the Circulation Air Blower Data for setting air temperature

rise.

CAUTION

!

Table 8 – Blower Speed Chart

Wire Color

Motor Speed

Black

High

Orange

*

Med---High

Blue

Medium

Red

Low

*

Med---High speed may not be provided on all models.

1. Refer to

Furnace Wiring Diagram

for location of the heat-

ing and cooling speed taps located on the furnace control

as well as location of unused blower motor speed leads.

Use the chart (Table 8) to determine the blower motor

speed settings.

2. Change the heat or cool blower motor speed by removing

the motor lead from the “

Heat

” or “

Cool

” terminal and

replace it with the desired motor speed lead from the

“Unused Motor Lead

” location. Connect the wire previ-

ously removed from the “

Heat

” or “

Cool

” terminal to the

vacated

“Unused Motor Lead

” terminal.

3. If the same speed must be used for both heating and cool-

ing, remove the undesired motor speed lead from the

“Heat

” or

“Cool

” terminal and connect that lead to the

open terminal at

“Unused Motor Lead

” location. Attach a

jumper between the “

Heat

” and “

Cool

” terminals and the

remaining motor speed lead.

NOTE

: For motors with (4) speed leads, it will be necessary to

tape off the terminal of the motor speed lead removed from the

Heat

” or “

Cool

” terminal with electrical tape since an open

terminal will not be available at the

“Unused Motor Lead

location.

Continuous- Fan Operation using “G”

Energizing the “G” terminal on the furnace control provides

continuous fan operation. This is done by connecting the G

terminal of the thermostat to the G terminal on the furnace

control. When the FAN switch is turned from auto to ON the fan

will operate continuously at “HEAT” speed.

EAC will be

energized in this mode.

NOTE

: In heating, the fan will turn off during furnace ignition

and warm up then restart at heating speed.

Hard Wired Continuous Fan Operation

A terminal is provided on the furnace control board located in the

circulating blower compartment for operation of the continuous

fan option. This connection is intended for the low speed motor

tap, and has a lower contact rating (8 amps) than the heat and

cool taps. When the low speed blower lead is connected to this

terminal, this will provide low speed blower operation whenever

the other two speeds (

Heat

or

Cool

) are not energized.

Thoroughly check the system after modification to ensure the

proper operation of the circulating air blower in all modes of

operation.

Separate Speed Selections for Heat, Cool,

and Continuous Fan

Connect low speed lead from circulating motor to the “

Cont.

terminal at the furnace control. The appropriate motor leads

should already be connected to the “

Heat

” and “

Cool

” terminals.

Heating and Continuous Blower Speed the

Same

If it is necessary to operate the heating speed and continuous

blower speed using the same blower speed, connect a jumper

between the “

Heat

” and “

Cont.

” terminals on the furnace

control.

NOTE

: There should be only

ONE

motor lead going to the

Heat

” and “

Cont.

” terminals.

FURNACE MAINTENANCE

FIRE,

EXPLOSION,

OR

CARBON

MONOXIDE

HAZARDS

Failure to follow this warning could result in personal injury,

death and/or property damage.
It is recommended that the furnace be inspected and serviced

on an annual basis (before the heating season) by a qualified

service technician.

!

WARNING

ELECTRICAL

SHOCK,

FIRE

OR

EXPLOSION

HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
Before servicing, disconnect all electrical power to furnace.

Lockout and tag with appropriate label.
When servicing controls, label all wires prior to disconnecting.

Reconnect wires correctly.
Verify proper operation after servicing.

!

WARNING

359AA

V

Summary of Contents for 4-WAY MULTIPOISE 359AAV

Page 1: ...sulted before installation to determine the need to obtain a permit IPEX System 636 is a trademark of IPEX Inc CONSIGNES SP CIALES POUR L IN STALLATION DE VENTILLATION AU CANADA L installation faite a...

Page 2: ...or of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 3: ...h unit and other safety precautions that may apply These instructions cover the minimum requirements and conform to existing national standards and safety codes In some instances these instructions ex...

Page 4: ...ldings or structures under construction S This furnace is NOT approved for installation in mobile homes trailers or recreation vehicles S Seal around supply and return air ducts S Install correct filt...

Page 5: ...to the plastic Transition box Squeeze the hose together near the end and quickly reconnect the 3 4 19 mm OD rubber hose to the stub on the condensate trap Secure with the hose clamp When you return ho...

Page 6: ...the floor S Located or physically protected from possible damage by a vehicle 10 Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in atti...

Page 7: ...For venting information literature contact www Bryant com with the complete model and serial number of the furnace On the Dual Certified furnace the vent and combustion air pipes attach to the furnace...

Page 8: ...2 122 2 27 318 177 5 609 6 30 2 249 2 177 8 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723 9 57 2 336 6 60 3 27 1016 19 1 587 4 98 4 Specifications are subj...

Page 9: ...t or masonry chimney Multistory venting is NOT permitted If this furnace is replacing a previously common vented furnace it may be necessary to resize the existing vent and chimney to prevent oversizi...

Page 10: ...322 cm2 33 3 sq in 215 cm2 25 sq in 161 cm2 6 152 mm EXAMPLE Determining Free Area Furnace 100 000 Furnace 100 000 Water Heater 30 000 Water Heater 30 000 Total Input 130 000 4 000 Total Input 130 000...

Page 11: ...idered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in 2 1 000 BTUH 4 400 mm2 kW of total input rating of al...

Page 12: ...ce can NOT be common vented or connected to any type B BW or L vent or vent connector nor to any portion of a factory built or masonry chimney If this furnace is replacing a previously common vented f...

Page 13: ...12 The minimum pipe run length is 2 6 M 13 The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing It can also be run in the same chase with a ven...

Page 14: ...are required the length can be INCREASED by 5 1 5 M for each additional elbow NOT used NOTE It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters t...

Page 15: ...15 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW A06675 Fig 7 Direct Vent Termination Clearance 359AAV...

Page 16: ...16 Fig 8 Other than Direct Vent Termination Clearance 359AAV...

Page 17: ...remain in the furnace between the door switch plate and the blower shelf Fig 9 during operation See Fig 19 for proper routing and installation of the overflow DO NOT trap the drain line in any other l...

Page 18: ...rommet in loose parts bag S Install the 1 2 13 mm CPVC street elbow on discharge of trap S Install the black PVC tube connector 3 4 18 mm PVC x 1 2 13 mm CPVC from loose parts bag as shown in the illu...

Page 19: ...of 2 51 mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 51 mm PVC tee or A 2 PVC coupling fastened onto the drain tee S Install tee trap in...

Page 20: ...the vent drain to the trap Secure all connections with clamps S Install the vent pipe grommet into the casing S Cut an appropriate length of 2 51 mm PVC pipe long enough to exit the cabinet and conne...

Page 21: ...to the left side of the unit using the two 2 screws provided Cut the 5 8 16 mm ID corrugated hose as shown above and fasten the 90 bend end to the trap and fasten the straight end to the transition dr...

Page 22: ...o the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Connect the corrugated drain tube from the transition box to the trap as shown If an e...

Page 23: ...he 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the trap Secure connections with clamps S Rem...

Page 24: ...e will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrug...

Page 25: ...Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from...

Page 26: ...will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugat...

Page 27: ...ig 18 that corresponds to the installation position of the furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe jo...

Page 28: ...til it bottoms out NOTE Cement MUST be fluid while inserting pipe If NOT recoat pipe 4 Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fittin...

Page 29: ...ng materials may be affected by flue products expelled in close proximity to unprotected surfaces Sealing or shielding of the exposed surfaces with a corrosion resistant material such as aluminum shee...

Page 30: ...Snow Level 36 Min 2 50 8mm Max 36 Min OR 914 4mm 914 4mm A07718 Fig 25 Concentric Vent and Combustion Air Roof Termination A Vent Dimension A is touching or 2 in 503 8mm maximum separation 25 22 02d...

Page 31: ...he installation from Table 4 and Fig 32 2 Determine the best location for the termination kit See Fig 31 for vertical termination or Fig 35 for horizontal termination Roof termination is preferred sin...

Page 32: ...Airflow restriction will occur and the furnace pressure switch may cause intermittent operation Drill clearance hole in rain cap and pilot hole in vent pipe Stainless steel screw Field supplied A07722...

Page 33: ...essures Combustion Air Vent Combustion Air Vent 45 Elbow Field Supplied 25 22 02 Strap Field Supplied Flush to 1 25 4mm max Note Securing strap must be field installed to prevent movement of termina t...

Page 34: ...in National Fuel Gas Code or CGA codes 3 Two stage regulation of Propane gas is recommended Propane Conversion FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or d...

Page 35: ...2 pressure switches Manual shut off valve Alternative installation Representative drawing only some models may vary in appearance A07724 Fig 36 Typical Gas Piping for Upflow Use elbows and 3 76 mm pip...

Page 36: ...s 6 and 7 Table 7 LPG or Propane Gas Manifold Pressure in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL Ft M 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000...

Page 37: ...injury and or loss of life WARNING 1 The furnace and the equipment shut off valve must be dis connected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 38: ...e 115V HUM called HUM on Control is energized when the inducer is energized ELECTRONIC AIR CLEANER EAC is energized when there is a blower speed call except is NOT energized when blower operates in th...

Page 39: ...ucts under the floor or through the attic 1 For side connections using a 16 x 25 406 x 635 mm filter cut out the embossed area shown in Fig 41 This will provide a 141 2 x 221 2 368 x 572 mm approxim a...

Page 40: ...unit to avoid condensation on the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the furnace This allows for installation in the horizontal right or...

Page 41: ...tent 1 Turn OFF gas supply to all appliances and start furnace Use jumper wire on R to W for Heat 2 Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution Re...

Page 42: ...inal will not be available at the Unused Motor Lead location Continuous Fan Operation using G Energizing the G terminal on the furnace control provides continuous fan operation This is done by connect...

Page 43: ...lve is energized the main burners light and flame is sensed S The igniter is de energized after the main burners ignite S FCB will delay blower operation for the 30 seconds timed from the opening of t...

Page 44: ...ger than two minutes 1 hr delay roll out switch requires manual reset 8 Flashes Permanent Lockout Gas valve relay contact stuck closed or miswired gas valve power reset only 10 Flashes Line voltage 11...

Reviews: