17

Condensate Drain Trap

This furnace removes both sensible and latent heat from the

products of combustion. Removal of the latent heat results in

condensation of the water vapor. The condensate is removed from

the furnace through the drains in the plastic transition and the

vent fitting. The drains connect to the externally mounted

condensate drain trap on the left or right side of the furnace.
The start--up of a new furnace will involve a cycle or two of the

furnace to properly prime the condensate trap with water. Until

the trap is fully primed, some condensate will be pulled into the

combustion blower. The furnace may cycle on the pressure switch

connected to the plastic transition box due to condensate buildup.

After the trap is primed, the condensate will start draining from

the furnace. The combustion blower will clear out any remaining

condensate in the blower housing through the vent fitting

downstream of the blower. Note that the condensate trap can also

be primed by pouring water into the

1

/

2

drain hose. Remove

the

1

/

2

ID drain hose from either the gutter or the white PVC tee

trap. Using a funnel pour eight (8) ounces of water into

1

/

2

(13

mm) ID drain hose. Water will flow through the drain hose and

into the condensate drain trap. This will prime both the vent and

the transition sides of the trap. Reconnect the

1

/

2

(13 mm) ID

drain hose to the original component, either the gutter or the PVC

tee trap.
The condensate drain trap supplied with the furnace MUST be

used. The drain connection on the condensate drain trap is sized

for

3

/

4

PVC or CPVC pipe, however alternate

1

/

2

(13 mm)

CPVC (nominal

5

/

8

O.D.) or vinyl tubing with a minimum inner

diameter (I.D.) of

5

/

8

may also be used, as allowed by local

codes. Alternate drain pipes and hoses may be used as allowed by

local codes.
The drain line must maintain a

1

/

4

(6 mm) per foot downward

slope toward the drain.

1

/

4

(6 mm) per foot is recommended.

Installation of an overflow line is recommended when the

1

/

4

(6

mm) per foot slope to the condensate drain cannot be maintained.

A drain tube clip is included in the furnace to prevent

kinking/buckling of the drain tube. The clip should remain in the

furnace (between the door switch plate and the blower shelf, Fig.

9) during operation. See Fig. 19 for proper routing and

installation of the overflow.
DO NOT trap the drain line in any other location than at the

condensate drain trap supplied with the furnace.

FROZEN AND BURST WATER PIPE HAZARD

Failure to follow this caution may result in property damage.
If a condensate pump is installed, a plugged condensate drain

or a failed pump may cause the furnace to shut down. Do

not leave the home unattended during freezing weather

without turning off water supply and draining water pipes or

otherwise protecting against the risk of frozen pipes.

CAUTION

!

If possible, DO NOT route the drain line where it may freeze.

The drain line must terminate at an inside drain to prevent

freezing of the condensate and possible property damage.

1. A condensate sump pump

MUST

be used if required by

local codes, or if no indoor floor drain is available. The

condensate pump must be approved for use with acidic

condensate.

2. A plugged condensate drain line or a failed condensate

pump will allow condensate to spill. If the furnace is in-

stalled where a condensate spill could cause damage, it is

recommended that an auxiliary safety switch be installed

to prevent operation of the equipment in the event of pump

failure or plugged drain line. If used, an auxiliary safety

switch should be installed in the R circuit (low voltage)

ONLY

.

3. If the auxiliary switch in the condensate pump is used, the

furnace may shut down due to a blocked condensate line

or failed pump. To prevent frozen water pipes see the

“Frozen Water Pipe Hazard” Installation Section of this

manual.

Drain Tube

Clip

Door
Switch

Blower
Shelf

Representative drawing only, some models may vary in appearance.

A07705

Fig. 9 -- Drain Tube Clip Location

Condensate Drain Trap Freeze Protection

Special precautions

MUST

be made if installing furnace in an

area which may drop below freezing. This can cause improper

operation or damage to the equipment. If the the furnace

environment has the potential of freezing, the drain trap and drain

line must be protected. Use 3 to 6 watt per foot at 115 volt, 40

°

F

(4

°

C) self--regulating shielded and waterproof heat tape. Wrap

the drain trap and drain line with the heat tape and secure with the

ties. Follow the heat tape manufacturer’s recommendations.

359AA

V

Summary of Contents for 4-WAY MULTIPOISE 359AAV

Page 1: ...sulted before installation to determine the need to obtain a permit IPEX System 636 is a trademark of IPEX Inc CONSIGNES SP CIALES POUR L IN STALLATION DE VENTILLATION AU CANADA L installation faite a...

Page 2: ...or of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 3: ...h unit and other safety precautions that may apply These instructions cover the minimum requirements and conform to existing national standards and safety codes In some instances these instructions ex...

Page 4: ...ldings or structures under construction S This furnace is NOT approved for installation in mobile homes trailers or recreation vehicles S Seal around supply and return air ducts S Install correct filt...

Page 5: ...to the plastic Transition box Squeeze the hose together near the end and quickly reconnect the 3 4 19 mm OD rubber hose to the stub on the condensate trap Secure with the hose clamp When you return ho...

Page 6: ...the floor S Located or physically protected from possible damage by a vehicle 10 Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in atti...

Page 7: ...For venting information literature contact www Bryant com with the complete model and serial number of the furnace On the Dual Certified furnace the vent and combustion air pipes attach to the furnace...

Page 8: ...2 122 2 27 318 177 5 609 6 30 2 249 2 177 8 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723 9 57 2 336 6 60 3 27 1016 19 1 587 4 98 4 Specifications are subj...

Page 9: ...t or masonry chimney Multistory venting is NOT permitted If this furnace is replacing a previously common vented furnace it may be necessary to resize the existing vent and chimney to prevent oversizi...

Page 10: ...322 cm2 33 3 sq in 215 cm2 25 sq in 161 cm2 6 152 mm EXAMPLE Determining Free Area Furnace 100 000 Furnace 100 000 Water Heater 30 000 Water Heater 30 000 Total Input 130 000 4 000 Total Input 130 000...

Page 11: ...idered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in 2 1 000 BTUH 4 400 mm2 kW of total input rating of al...

Page 12: ...ce can NOT be common vented or connected to any type B BW or L vent or vent connector nor to any portion of a factory built or masonry chimney If this furnace is replacing a previously common vented f...

Page 13: ...12 The minimum pipe run length is 2 6 M 13 The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing It can also be run in the same chase with a ven...

Page 14: ...are required the length can be INCREASED by 5 1 5 M for each additional elbow NOT used NOTE It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters t...

Page 15: ...15 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW A06675 Fig 7 Direct Vent Termination Clearance 359AAV...

Page 16: ...16 Fig 8 Other than Direct Vent Termination Clearance 359AAV...

Page 17: ...remain in the furnace between the door switch plate and the blower shelf Fig 9 during operation See Fig 19 for proper routing and installation of the overflow DO NOT trap the drain line in any other l...

Page 18: ...rommet in loose parts bag S Install the 1 2 13 mm CPVC street elbow on discharge of trap S Install the black PVC tube connector 3 4 18 mm PVC x 1 2 13 mm CPVC from loose parts bag as shown in the illu...

Page 19: ...of 2 51 mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 51 mm PVC tee or A 2 PVC coupling fastened onto the drain tee S Install tee trap in...

Page 20: ...the vent drain to the trap Secure all connections with clamps S Install the vent pipe grommet into the casing S Cut an appropriate length of 2 51 mm PVC pipe long enough to exit the cabinet and conne...

Page 21: ...to the left side of the unit using the two 2 screws provided Cut the 5 8 16 mm ID corrugated hose as shown above and fasten the 90 bend end to the trap and fasten the straight end to the transition dr...

Page 22: ...o the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Connect the corrugated drain tube from the transition box to the trap as shown If an e...

Page 23: ...he 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the trap Secure connections with clamps S Rem...

Page 24: ...e will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrug...

Page 25: ...Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from...

Page 26: ...will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugat...

Page 27: ...ig 18 that corresponds to the installation position of the furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe jo...

Page 28: ...til it bottoms out NOTE Cement MUST be fluid while inserting pipe If NOT recoat pipe 4 Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fittin...

Page 29: ...ng materials may be affected by flue products expelled in close proximity to unprotected surfaces Sealing or shielding of the exposed surfaces with a corrosion resistant material such as aluminum shee...

Page 30: ...Snow Level 36 Min 2 50 8mm Max 36 Min OR 914 4mm 914 4mm A07718 Fig 25 Concentric Vent and Combustion Air Roof Termination A Vent Dimension A is touching or 2 in 503 8mm maximum separation 25 22 02d...

Page 31: ...he installation from Table 4 and Fig 32 2 Determine the best location for the termination kit See Fig 31 for vertical termination or Fig 35 for horizontal termination Roof termination is preferred sin...

Page 32: ...Airflow restriction will occur and the furnace pressure switch may cause intermittent operation Drill clearance hole in rain cap and pilot hole in vent pipe Stainless steel screw Field supplied A07722...

Page 33: ...essures Combustion Air Vent Combustion Air Vent 45 Elbow Field Supplied 25 22 02 Strap Field Supplied Flush to 1 25 4mm max Note Securing strap must be field installed to prevent movement of termina t...

Page 34: ...in National Fuel Gas Code or CGA codes 3 Two stage regulation of Propane gas is recommended Propane Conversion FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or d...

Page 35: ...2 pressure switches Manual shut off valve Alternative installation Representative drawing only some models may vary in appearance A07724 Fig 36 Typical Gas Piping for Upflow Use elbows and 3 76 mm pip...

Page 36: ...s 6 and 7 Table 7 LPG or Propane Gas Manifold Pressure in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL Ft M 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000...

Page 37: ...injury and or loss of life WARNING 1 The furnace and the equipment shut off valve must be dis connected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 38: ...e 115V HUM called HUM on Control is energized when the inducer is energized ELECTRONIC AIR CLEANER EAC is energized when there is a blower speed call except is NOT energized when blower operates in th...

Page 39: ...ucts under the floor or through the attic 1 For side connections using a 16 x 25 406 x 635 mm filter cut out the embossed area shown in Fig 41 This will provide a 141 2 x 221 2 368 x 572 mm approxim a...

Page 40: ...unit to avoid condensation on the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the furnace This allows for installation in the horizontal right or...

Page 41: ...tent 1 Turn OFF gas supply to all appliances and start furnace Use jumper wire on R to W for Heat 2 Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution Re...

Page 42: ...inal will not be available at the Unused Motor Lead location Continuous Fan Operation using G Energizing the G terminal on the furnace control provides continuous fan operation This is done by connect...

Page 43: ...lve is energized the main burners light and flame is sensed S The igniter is de energized after the main burners ignite S FCB will delay blower operation for the 30 seconds timed from the opening of t...

Page 44: ...ger than two minutes 1 hr delay roll out switch requires manual reset 8 Flashes Permanent Lockout Gas valve relay contact stuck closed or miswired gas valve power reset only 10 Flashes Line voltage 11...

Reviews: