Bryant 4-WAY MULTIPOISE 359AAV Installation Instructions Manual Download Page 10

10

d. Vertical duct openings or openings directly communic-

ating with the outdoors require 1 square inch of free

area per 4,000 BTUH (5.5 cm

2

/kW) for combined in-

put of all gas appliances in the space

(

see

Table 1).

3. When one permanent outdoor opening is used, the opening

requires:

a. 1 sq. in of free area per 3,000 BTUH (7 cm

2

/kW) for

combined input of all gas appliances in the space (see

Table 1) and

b. not less than the sum of the areas of all vent connect-

ors in the space.

The opening shall commence within 12

(305 mm) of the top of

the enclosure. Appliances shall have clearances of at least 1

(25

mm) from the sides and back and 6

from the front. The opening

shall directly communicate with the outdoors or shall

communicate through a vertical or horizontal duct to the outdoors

or spaces (crawl or attic) that freely communicate with the

outdoors.

4. Combination of Indoor and Outdoor Air shall have:

a. Indoor openings that comply with the

Indoor Com-

bustion Air

Method below and

b. Outdoor openings located as required in the

Outdoor

Combustion Air

Method above and

c. Outdoor openings sized as follows.

(1.) Calculate the

Ratio

of all Indoor Space volume

divided by required volume for

Indoor Combus-

tion Air

Method.

(2.) Outdoor opening size reduction

Factor

is

1

minus

the

Ratio

in 1) above.

(3.) Minimum size of Outdoor openings shall be the

size required in

Outdoor Combustion Air

Meth-

od above multiplied by reduction

Factor

.

Table 1 – Free Area

BTUH

Input

Rating

Minimum Free Area Required for Each Opening or Duct to Outdoors

Two Horizontal Ducts

(sq. in./2,000 BTUH)

Single Opening

(sq. in./3,000 BTUH)

Two Vertical Ducts or Open-

ings

(sq. in./4,000 BTUH)

Round Duct

(sq. in. /4,000

BTUH)

60,000

30 sq. in. (194 cm

2

)

20 sq. in. (129 cm

2

)

15 sq. in. (97 cm

2

)

5

(127 mm)

80,000

40 sq. in. (258 cm

2

)

26.7 sq. in. (172 cm

2

)

20.0 sq. in. (129 cm

2

)

5

(127 mm)

100,000

50 sq. in. (322 cm

2

)

33.3 sq. in. (215 cm

2

)

25 sq. in. (161 cm

2

)

6

(152 mm)

EXAMPLE:

Determining Free Area

Furnace
100,000
Furnace
100,000

+

+

Water Heater

30,000

Water Heater

30,000

=

=

Total Input

(130,000

÷

4,000)

Total Input

(130,000

÷

2,000)

=

32.5 Sq. In. Vertical

=

65 Sq. In. Horizontal

Indoor Combustion Air (Unconfined Space)

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or

death.
Most homes will require additional air from outdoors for

combustion and ventilation. A space with at least 50 cubic

feet per 1,000 Btuh (4.8 M

3

/kW) Input rating or homes with

tight construction may need outdoor air, supplied through

ducts, to supplement air infiltration for proper combustion and

ventilation of flue gasses.

!

WARNING

Standard

and

Known- Air- Infiltration Rate

Methods

©

NFPA & AGA

Indoor air

is permitted for combustion and ventilation, if the

Standard

or

Known--Air--Infiltration Rate

Method is used.

The

Standard

Method may be used, if the space has no less

volume than 50 cubic feet per 1,000 BTUH (4.8 M

3

/kW) input

rating for all gas appliances installed in the space. The

standard

method permits indoor air to be used for combustion and

ventilation air.
The

Known Air Infiltration Rate

Method shall be used if the

infiltration rate is known to be less than 0.40 air changes per hour

(ACH) and equal to or greater than 0.10 ACH. Infiltration rates

greater than 0.60 ACH shall not be used. The minimum required

volume of the space varies with the number of ACH and shall be

determined per

Table 2

or

Equations 1 and 2

. Determine the

minimum required volume for each appliance in the space, and

add the volumes together to get the total minimum required

volume for the space.

CARBON MONOXIDE POISONING HAZARD

Failure to supply additional air by means of ventilation grilles

or ducts could result in personal injury or death.
An unconfined space or homes with tight construction may not

have adequate air infiltration for proper combustion and

ventilation of flue gasses. Most homes will require additional

air.

!

WARNING

359AA

V

Summary of Contents for 4-WAY MULTIPOISE 359AAV

Page 1: ...sulted before installation to determine the need to obtain a permit IPEX System 636 is a trademark of IPEX Inc CONSIGNES SP CIALES POUR L IN STALLATION DE VENTILLATION AU CANADA L installation faite a...

Page 2: ...or of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 3: ...h unit and other safety precautions that may apply These instructions cover the minimum requirements and conform to existing national standards and safety codes In some instances these instructions ex...

Page 4: ...ldings or structures under construction S This furnace is NOT approved for installation in mobile homes trailers or recreation vehicles S Seal around supply and return air ducts S Install correct filt...

Page 5: ...to the plastic Transition box Squeeze the hose together near the end and quickly reconnect the 3 4 19 mm OD rubber hose to the stub on the condensate trap Secure with the hose clamp When you return ho...

Page 6: ...the floor S Located or physically protected from possible damage by a vehicle 10 Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in atti...

Page 7: ...For venting information literature contact www Bryant com with the complete model and serial number of the furnace On the Dual Certified furnace the vent and combustion air pipes attach to the furnace...

Page 8: ...2 122 2 27 318 177 5 609 6 30 2 249 2 177 8 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723 9 57 2 336 6 60 3 27 1016 19 1 587 4 98 4 Specifications are subj...

Page 9: ...t or masonry chimney Multistory venting is NOT permitted If this furnace is replacing a previously common vented furnace it may be necessary to resize the existing vent and chimney to prevent oversizi...

Page 10: ...322 cm2 33 3 sq in 215 cm2 25 sq in 161 cm2 6 152 mm EXAMPLE Determining Free Area Furnace 100 000 Furnace 100 000 Water Heater 30 000 Water Heater 30 000 Total Input 130 000 4 000 Total Input 130 000...

Page 11: ...idered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in 2 1 000 BTUH 4 400 mm2 kW of total input rating of al...

Page 12: ...ce can NOT be common vented or connected to any type B BW or L vent or vent connector nor to any portion of a factory built or masonry chimney If this furnace is replacing a previously common vented f...

Page 13: ...12 The minimum pipe run length is 2 6 M 13 The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing It can also be run in the same chase with a ven...

Page 14: ...are required the length can be INCREASED by 5 1 5 M for each additional elbow NOT used NOTE It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters t...

Page 15: ...15 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW A06675 Fig 7 Direct Vent Termination Clearance 359AAV...

Page 16: ...16 Fig 8 Other than Direct Vent Termination Clearance 359AAV...

Page 17: ...remain in the furnace between the door switch plate and the blower shelf Fig 9 during operation See Fig 19 for proper routing and installation of the overflow DO NOT trap the drain line in any other l...

Page 18: ...rommet in loose parts bag S Install the 1 2 13 mm CPVC street elbow on discharge of trap S Install the black PVC tube connector 3 4 18 mm PVC x 1 2 13 mm CPVC from loose parts bag as shown in the illu...

Page 19: ...of 2 51 mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 51 mm PVC tee or A 2 PVC coupling fastened onto the drain tee S Install tee trap in...

Page 20: ...the vent drain to the trap Secure all connections with clamps S Install the vent pipe grommet into the casing S Cut an appropriate length of 2 51 mm PVC pipe long enough to exit the cabinet and conne...

Page 21: ...to the left side of the unit using the two 2 screws provided Cut the 5 8 16 mm ID corrugated hose as shown above and fasten the 90 bend end to the trap and fasten the straight end to the transition dr...

Page 22: ...o the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Connect the corrugated drain tube from the transition box to the trap as shown If an e...

Page 23: ...he 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the trap Secure connections with clamps S Rem...

Page 24: ...e will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrug...

Page 25: ...Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from...

Page 26: ...will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugat...

Page 27: ...ig 18 that corresponds to the installation position of the furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe jo...

Page 28: ...til it bottoms out NOTE Cement MUST be fluid while inserting pipe If NOT recoat pipe 4 Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fittin...

Page 29: ...ng materials may be affected by flue products expelled in close proximity to unprotected surfaces Sealing or shielding of the exposed surfaces with a corrosion resistant material such as aluminum shee...

Page 30: ...Snow Level 36 Min 2 50 8mm Max 36 Min OR 914 4mm 914 4mm A07718 Fig 25 Concentric Vent and Combustion Air Roof Termination A Vent Dimension A is touching or 2 in 503 8mm maximum separation 25 22 02d...

Page 31: ...he installation from Table 4 and Fig 32 2 Determine the best location for the termination kit See Fig 31 for vertical termination or Fig 35 for horizontal termination Roof termination is preferred sin...

Page 32: ...Airflow restriction will occur and the furnace pressure switch may cause intermittent operation Drill clearance hole in rain cap and pilot hole in vent pipe Stainless steel screw Field supplied A07722...

Page 33: ...essures Combustion Air Vent Combustion Air Vent 45 Elbow Field Supplied 25 22 02 Strap Field Supplied Flush to 1 25 4mm max Note Securing strap must be field installed to prevent movement of termina t...

Page 34: ...in National Fuel Gas Code or CGA codes 3 Two stage regulation of Propane gas is recommended Propane Conversion FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or d...

Page 35: ...2 pressure switches Manual shut off valve Alternative installation Representative drawing only some models may vary in appearance A07724 Fig 36 Typical Gas Piping for Upflow Use elbows and 3 76 mm pip...

Page 36: ...s 6 and 7 Table 7 LPG or Propane Gas Manifold Pressure in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL Ft M 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000...

Page 37: ...injury and or loss of life WARNING 1 The furnace and the equipment shut off valve must be dis connected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 38: ...e 115V HUM called HUM on Control is energized when the inducer is energized ELECTRONIC AIR CLEANER EAC is energized when there is a blower speed call except is NOT energized when blower operates in th...

Page 39: ...ucts under the floor or through the attic 1 For side connections using a 16 x 25 406 x 635 mm filter cut out the embossed area shown in Fig 41 This will provide a 141 2 x 221 2 368 x 572 mm approxim a...

Page 40: ...unit to avoid condensation on the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the furnace This allows for installation in the horizontal right or...

Page 41: ...tent 1 Turn OFF gas supply to all appliances and start furnace Use jumper wire on R to W for Heat 2 Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution Re...

Page 42: ...inal will not be available at the Unused Motor Lead location Continuous Fan Operation using G Energizing the G terminal on the furnace control provides continuous fan operation This is done by connect...

Page 43: ...lve is energized the main burners light and flame is sensed S The igniter is de energized after the main burners ignite S FCB will delay blower operation for the 30 seconds timed from the opening of t...

Page 44: ...ger than two minutes 1 hr delay roll out switch requires manual reset 8 Flashes Permanent Lockout Gas valve relay contact stuck closed or miswired gas valve power reset only 10 Flashes Line voltage 11...

Reviews: