background image

28

Rubber Coupling
& Clamps

90

°

Elbow

Combustion
Blower

Vent Fitting
& Clamps

Vent Extension
Pipe (Side Panel
Exit)

Vent Pipe
(Top Panel Exit)

Vent Pipe

Rotate downward
5

°

to 10

°

NOTE:

Built--in channel will be angled 5

°

to 10

°

also.

SIDE VIEW

NOTE:

The 90

°

elbow is approved

for use inside the furnace ONLY.

Tee

A07714

Fig. 20 -- Proper Sealing Procedure for Combustion Blower

Joining Pipe and Fittings

SEE VENT AND COMBUSTION AIR PIPING, vent and

Combustion Air Piping Guidelines

in this manual for applicable

ASTM Standards for vent materials.

FIRE HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
Observe all cautions and warnings printed on material

containers.
Provide adequate ventilation and do NOT assemble near heat

source or open flame. Do NOT smoke while using solvent

cements and avoid contact with skin or eyes.

!

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or

death.
Do NOT use solvent cement that has become curdled, lumpy

or thickened and do NOT thin. Observe precautions printed

on containers. For applications below 32

_

F (0

_

C), use only

low temperature type solvent cement. Poor joints may lead to

disconnected or leaking vent pipe joints allowing carbon

monoxide to enter the living space.

!

WARNING

1. Cut pipe end square, remove ragged edges and burrs.

Chamfer end of pipe, then clean fitting, socket and pipe

joint of all dirt, grease, or moisture.

NOTE

: Stir the solvent cement frequently while using. Use a

natural bristle brush or the dauber supplied with the cement. The
proper brush size is one inch.

2. After checking pipe and socket for proper fit, wipe socket

and pipe with cleaner-primer. Apply a liberal coat of

primer to inside surface of socket and outside of pipe. Do

NOT

allow primer to dry before applying cement.

3. Apply a thin coat of cement evenly in the socket. Quickly

apply a heavy coat of cement to the pipe end and insert

pipe into fittings with a slight twisting movement until it

bottoms out.

NOTE

: Cement

MUST

be fluid while inserting pipe. If

NOT,

recoat pipe.

4. Hold the pipe in the fitting for 30 seconds to prevent the

tapered socket from pushing the pipe out of the fitting.

5. Wipe all excess cement from the joint with a rag. Allow 15

minutes before handling. Cure time varies according to fit,

temperature and humidity.

Connecting Vent Pipes and Termination

(Direct Vent)

NOTE

: For direct vent applications, combustion air intake and

vent

MUST

terminate in the same atmospheric pressure zone. If

installation is in a cold climate (sustained temperatures 0

°

F

(--18

°

C)and below for 24 or more consecutive hours), increase

the minimum distance between vent pipe and air intake from 8

to 18

(203 to 457 mm).

1. Install all couplings, nipples and elbows using proper pro-

cedures for

Joining Pipe and Fittings

and maintain spa-

cing between vent and combustion air piping as indicated

in Fig. 21 through Fig. 23.

8” 203.2mm* MIN.

20’(6.1m) MAX

8” (203.2mm)

MIN.

*18 in. (457.2mm) Minimum for
cold climates (sustained tem-
peratures 0

°

F(- 17

°

C) and below

for 24 or more consecutive
hours)

GRADE LEVEL

OR

12 ”

(304.8mm)

MIN.

EXHAUST

INLET

A07715

Fig. 21 -- Sidewall Termination 12” (305 mm) or More Above

Snow Level or Grade Level

Horizontal Termination

1. Cut two holes. 2--

1

/

2

(64 mm) for 2

(51 mm) pipe, 3

(76

mm) for 2--

1

/

2

(64 mm) pipe, or 3

1

/

2

(89 mm) for 3

(76

mm) pipe. Do

NOT

make the holes oversized, or it will be

necessary to add a sheet metal or plywood plate on the

outside with the correct size hole in it.

2. Check hole sizes by making sure it is smaller than the

couplings or elbows that will be installed on the outside.

The couplings or elbows

MUST

prevent the pipe from be-

ing pushed back through the wall.

3. Extend vent pipe and combustion air pipe through the wall

3

/

4

(19 mm) to 1

(25 mm) and seal area between pipe

and wall.

4. Install the couplings, nipple and termination elbows as

shown and maintain spacing between vent and combustion

air piping as indicated in Fig. 21 and Fig. 22.

A metal shield is recommended 18

x 18

(457 mm x 457 mm)

min. or 18

(457 mm) min. diameter around the vent termination

at the exterior wall to protect the house exterior materials from

flue product or condensation (freezing) damage.

359AA

V

Summary of Contents for 4-WAY MULTIPOISE 359AAV

Page 1: ...sulted before installation to determine the need to obtain a permit IPEX System 636 is a trademark of IPEX Inc CONSIGNES SP CIALES POUR L IN STALLATION DE VENTILLATION AU CANADA L installation faite a...

Page 2: ...or of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 3: ...h unit and other safety precautions that may apply These instructions cover the minimum requirements and conform to existing national standards and safety codes In some instances these instructions ex...

Page 4: ...ldings or structures under construction S This furnace is NOT approved for installation in mobile homes trailers or recreation vehicles S Seal around supply and return air ducts S Install correct filt...

Page 5: ...to the plastic Transition box Squeeze the hose together near the end and quickly reconnect the 3 4 19 mm OD rubber hose to the stub on the condensate trap Secure with the hose clamp When you return ho...

Page 6: ...the floor S Located or physically protected from possible damage by a vehicle 10 Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in atti...

Page 7: ...For venting information literature contact www Bryant com with the complete model and serial number of the furnace On the Dual Certified furnace the vent and combustion air pipes attach to the furnace...

Page 8: ...2 122 2 27 318 177 5 609 6 30 2 249 2 177 8 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723 9 57 2 336 6 60 3 27 1016 19 1 587 4 98 4 Specifications are subj...

Page 9: ...t or masonry chimney Multistory venting is NOT permitted If this furnace is replacing a previously common vented furnace it may be necessary to resize the existing vent and chimney to prevent oversizi...

Page 10: ...322 cm2 33 3 sq in 215 cm2 25 sq in 161 cm2 6 152 mm EXAMPLE Determining Free Area Furnace 100 000 Furnace 100 000 Water Heater 30 000 Water Heater 30 000 Total Input 130 000 4 000 Total Input 130 000...

Page 11: ...idered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in 2 1 000 BTUH 4 400 mm2 kW of total input rating of al...

Page 12: ...ce can NOT be common vented or connected to any type B BW or L vent or vent connector nor to any portion of a factory built or masonry chimney If this furnace is replacing a previously common vented f...

Page 13: ...12 The minimum pipe run length is 2 6 M 13 The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing It can also be run in the same chase with a ven...

Page 14: ...are required the length can be INCREASED by 5 1 5 M for each additional elbow NOT used NOTE It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters t...

Page 15: ...15 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW A06675 Fig 7 Direct Vent Termination Clearance 359AAV...

Page 16: ...16 Fig 8 Other than Direct Vent Termination Clearance 359AAV...

Page 17: ...remain in the furnace between the door switch plate and the blower shelf Fig 9 during operation See Fig 19 for proper routing and installation of the overflow DO NOT trap the drain line in any other l...

Page 18: ...rommet in loose parts bag S Install the 1 2 13 mm CPVC street elbow on discharge of trap S Install the black PVC tube connector 3 4 18 mm PVC x 1 2 13 mm CPVC from loose parts bag as shown in the illu...

Page 19: ...of 2 51 mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 51 mm PVC tee or A 2 PVC coupling fastened onto the drain tee S Install tee trap in...

Page 20: ...the vent drain to the trap Secure all connections with clamps S Install the vent pipe grommet into the casing S Cut an appropriate length of 2 51 mm PVC pipe long enough to exit the cabinet and conne...

Page 21: ...to the left side of the unit using the two 2 screws provided Cut the 5 8 16 mm ID corrugated hose as shown above and fasten the 90 bend end to the trap and fasten the straight end to the transition dr...

Page 22: ...o the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Connect the corrugated drain tube from the transition box to the trap as shown If an e...

Page 23: ...he 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the trap Secure connections with clamps S Rem...

Page 24: ...e will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrug...

Page 25: ...Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from...

Page 26: ...will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugat...

Page 27: ...ig 18 that corresponds to the installation position of the furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe jo...

Page 28: ...til it bottoms out NOTE Cement MUST be fluid while inserting pipe If NOT recoat pipe 4 Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fittin...

Page 29: ...ng materials may be affected by flue products expelled in close proximity to unprotected surfaces Sealing or shielding of the exposed surfaces with a corrosion resistant material such as aluminum shee...

Page 30: ...Snow Level 36 Min 2 50 8mm Max 36 Min OR 914 4mm 914 4mm A07718 Fig 25 Concentric Vent and Combustion Air Roof Termination A Vent Dimension A is touching or 2 in 503 8mm maximum separation 25 22 02d...

Page 31: ...he installation from Table 4 and Fig 32 2 Determine the best location for the termination kit See Fig 31 for vertical termination or Fig 35 for horizontal termination Roof termination is preferred sin...

Page 32: ...Airflow restriction will occur and the furnace pressure switch may cause intermittent operation Drill clearance hole in rain cap and pilot hole in vent pipe Stainless steel screw Field supplied A07722...

Page 33: ...essures Combustion Air Vent Combustion Air Vent 45 Elbow Field Supplied 25 22 02 Strap Field Supplied Flush to 1 25 4mm max Note Securing strap must be field installed to prevent movement of termina t...

Page 34: ...in National Fuel Gas Code or CGA codes 3 Two stage regulation of Propane gas is recommended Propane Conversion FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or d...

Page 35: ...2 pressure switches Manual shut off valve Alternative installation Representative drawing only some models may vary in appearance A07724 Fig 36 Typical Gas Piping for Upflow Use elbows and 3 76 mm pip...

Page 36: ...s 6 and 7 Table 7 LPG or Propane Gas Manifold Pressure in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL Ft M 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000...

Page 37: ...injury and or loss of life WARNING 1 The furnace and the equipment shut off valve must be dis connected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 38: ...e 115V HUM called HUM on Control is energized when the inducer is energized ELECTRONIC AIR CLEANER EAC is energized when there is a blower speed call except is NOT energized when blower operates in th...

Page 39: ...ucts under the floor or through the attic 1 For side connections using a 16 x 25 406 x 635 mm filter cut out the embossed area shown in Fig 41 This will provide a 141 2 x 221 2 368 x 572 mm approxim a...

Page 40: ...unit to avoid condensation on the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the furnace This allows for installation in the horizontal right or...

Page 41: ...tent 1 Turn OFF gas supply to all appliances and start furnace Use jumper wire on R to W for Heat 2 Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution Re...

Page 42: ...inal will not be available at the Unused Motor Lead location Continuous Fan Operation using G Energizing the G terminal on the furnace control provides continuous fan operation This is done by connect...

Page 43: ...lve is energized the main burners light and flame is sensed S The igniter is de energized after the main burners ignite S FCB will delay blower operation for the 30 seconds timed from the opening of t...

Page 44: ...ger than two minutes 1 hr delay roll out switch requires manual reset 8 Flashes Permanent Lockout Gas valve relay contact stuck closed or miswired gas valve power reset only 10 Flashes Line voltage 11...

Reviews: