background image

13

Applicable ASTM Standards for Vent Materials

Materials

Sch. 40

Pipe

SDR

Pipe

Cell

Core

Pipe

Fittings

Primer

Solvent

Cement

ABS

D1527

__

F628

D2468

&

D2661

--- ---

D2235

PVC

D1785

D2241

F891

D2466

&

D2665

F656

D2564

CPVC

F441

F442

--- ---

F438

--- ---

F493

ABS to

PVC

--- ---

--- ---

--- ---

--- ---

--- ---

D3138

NOTE

:

1. In Canada, all pipe, fittings & cements must conform to

applicable CSA standards or to local codes having juris-

diction.

2. Only use solvent cements that are marked for use with the

specific venting material.

3. ABS to PVC transition joints REQUIRE a special solvent

cement that meets the requirements of ASTM D3138.

4. Refer to ASTM D2855 for general procedure to use for

cementing plastic pipe and fittings.

NOTE

: In order to create a seal that allows future removal of

pipe,

RTV sealant MUST be used on the inlet pipe

where it

joins to the furnace.

NOTE

: All vent piping

MUS

T be installed in compliance with

local codes or ordinances, these instructions, good trade practices,
and codes of country having jurisdiction.

1. Determine the best routing and termination for the vent

pipe and air inlet pipe by referring to all of the instructions

and guidelines in this Section.

2. Determine the size required for the vent pipe and air inlet

pipe.

3. Loosely assemble all venting parts without adhesive (pipe

joint cement) for correct fit before final assembly.

4. Furnace shall be installed so as to prevent the accumula-

tion of condensate.

5. Use of vertical piping is preferred because there will be

some moisture in the flue gases that may condense as it

leaves the vent pipe (See

Instructions For Horizontal

Vents

).

6. The vertical vent pipe

MUST

be supported so that no

weight is allowed to rest on the combustion blower.

7. Exhaust vent piping or air inlet piping diameter

MUST

NOT

be reduced.

8. All exhaust vent piping from the furnace to termination

MUST

slope upwards. A minimum of

1

/

4

(6 mm) per foot

of run is required to properly return condensate to the fur-

nace drain system.

9. Use DWV type long radius elbows whenever possible, as

they provide for the minimum slope on horizontal runs and

they provide less resistance in the vent system. If DWV

elbows cannot be used, use two, 45

°

elbows when pos-

sible. On horizontal runs the elbows can be slightly mis-

aligned to provide the correct slope.

10. All horizontal pipe runs

MUST

be supported at least every

five feet with galvanized strap or other rust resistant ma-

terial.

NO

sags or dips are permitted.

11. All vertical pipe runs

MUST

be supported every six feet

where accessible.

12. The minimum pipe run length is 2

(.6 M).

13. The piping can be run in the same chase or adjacent to

supply or vent pipe for water supply or waste plumbing. It

can also be run in the same chase with a vent from another

90+ furnace.

NOTE

: In

NO

case can the piping be run in a chase where

temperatures can exceed 140

°

F (60

°

C). or where radiated heat

from adjacent surfaces would exceed 140

°

F (60

°

C).

14. The vent outlet

MUST

be installed to terminate in the

same atmospheric pressure zone as the combustion air in-

let.

15. The vent system can be installed in an existing unused

chimney provided that:

S

Both the exhaust vent and air intake run the length of the
chimney.

S

No other gas fired appliance or fireplace (solid fuel) is vented
into the chimney.

S

The top of the chimney

MUST

be sealed flush or crowned up

to seal against rain or melting snow so

ONLY

the piping

protrudes.

S

The termination clearances shown in Fig. 7 and 8 are
maintained.

16. Furnace applications with vertical vents requiring vent dia-

meter increaser fittings

must

have increaser fittings in-

stalled in vertical portion of the vent. Condensate will be

trapped in the vent if the vent diameter is increased prior

to having an elbow turned upward. This could cause nuis-

ance tripping of the pressure switch.

Combustion Air and Vent Piping Insulation

Guidelines

NOTE

: Use closed cell, neoprene insulation or equivalent. If

Fiberglass or equivalent insulation is used it must have a vapor
barrier. Use R values of 7 up to 10

, (2.1 -- 3.0 M) R--11 if

exposure exceeds 10

. If Fiberglass insulation is used, exterior to

the structure, the pipe

MUST

be boxed in and sealed against

moisture.

1. When the vent or combustion air pipe height above the

roof exceeds 30

(762 mm), or if an exterior vertical riser is

used on a horizontal vent to get above snow levels, the ex-

terior portion

MUST

be insulated.

2. When combustion air inlet piping is installed above a sus-

pended ceiling, the pipe

MUST

be insulated with moisture

resistant insulation such as Armaflex or other equivalent

type of insulation.

3. Insulate combustion air inlet piping when run in warm, hu-

mid spaces.

Sizing Combustion Air and Vent Pipe

Consult

Table 3

to select the proper diameter exhaust and

combustion air piping. Exhaust and combustion air piping is sized

for each furnace BTUH size based on total lineal vent length (on

inlet

or

outlet side), and number of 90

°

elbows required. Two 45

°

elbows can be substituted for one 90

°

elbow. The elbow or

elbows used for vent termination outside the structure

ARE

counted, including elbows needed to bring termination above

expected snow levels. The elbow inside the furnace on the

359AAV

IS NOT

included in the count.

359AA

V

Summary of Contents for 4-WAY MULTIPOISE 359AAV

Page 1: ...sulted before installation to determine the need to obtain a permit IPEX System 636 is a trademark of IPEX Inc CONSIGNES SP CIALES POUR L IN STALLATION DE VENTILLATION AU CANADA L installation faite a...

Page 2: ...or of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 3: ...h unit and other safety precautions that may apply These instructions cover the minimum requirements and conform to existing national standards and safety codes In some instances these instructions ex...

Page 4: ...ldings or structures under construction S This furnace is NOT approved for installation in mobile homes trailers or recreation vehicles S Seal around supply and return air ducts S Install correct filt...

Page 5: ...to the plastic Transition box Squeeze the hose together near the end and quickly reconnect the 3 4 19 mm OD rubber hose to the stub on the condensate trap Secure with the hose clamp When you return ho...

Page 6: ...the floor S Located or physically protected from possible damage by a vehicle 10 Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in atti...

Page 7: ...For venting information literature contact www Bryant com with the complete model and serial number of the furnace On the Dual Certified furnace the vent and combustion air pipes attach to the furnace...

Page 8: ...2 122 2 27 318 177 5 609 6 30 2 249 2 177 8 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723 9 57 2 336 6 60 3 27 1016 19 1 587 4 98 4 Specifications are subj...

Page 9: ...t or masonry chimney Multistory venting is NOT permitted If this furnace is replacing a previously common vented furnace it may be necessary to resize the existing vent and chimney to prevent oversizi...

Page 10: ...322 cm2 33 3 sq in 215 cm2 25 sq in 161 cm2 6 152 mm EXAMPLE Determining Free Area Furnace 100 000 Furnace 100 000 Water Heater 30 000 Water Heater 30 000 Total Input 130 000 4 000 Total Input 130 000...

Page 11: ...idered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in 2 1 000 BTUH 4 400 mm2 kW of total input rating of al...

Page 12: ...ce can NOT be common vented or connected to any type B BW or L vent or vent connector nor to any portion of a factory built or masonry chimney If this furnace is replacing a previously common vented f...

Page 13: ...12 The minimum pipe run length is 2 6 M 13 The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing It can also be run in the same chase with a ven...

Page 14: ...are required the length can be INCREASED by 5 1 5 M for each additional elbow NOT used NOTE It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters t...

Page 15: ...15 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW A06675 Fig 7 Direct Vent Termination Clearance 359AAV...

Page 16: ...16 Fig 8 Other than Direct Vent Termination Clearance 359AAV...

Page 17: ...remain in the furnace between the door switch plate and the blower shelf Fig 9 during operation See Fig 19 for proper routing and installation of the overflow DO NOT trap the drain line in any other l...

Page 18: ...rommet in loose parts bag S Install the 1 2 13 mm CPVC street elbow on discharge of trap S Install the black PVC tube connector 3 4 18 mm PVC x 1 2 13 mm CPVC from loose parts bag as shown in the illu...

Page 19: ...of 2 51 mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 51 mm PVC tee or A 2 PVC coupling fastened onto the drain tee S Install tee trap in...

Page 20: ...the vent drain to the trap Secure all connections with clamps S Install the vent pipe grommet into the casing S Cut an appropriate length of 2 51 mm PVC pipe long enough to exit the cabinet and conne...

Page 21: ...to the left side of the unit using the two 2 screws provided Cut the 5 8 16 mm ID corrugated hose as shown above and fasten the 90 bend end to the trap and fasten the straight end to the transition dr...

Page 22: ...o the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Connect the corrugated drain tube from the transition box to the trap as shown If an e...

Page 23: ...he 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the trap Secure connections with clamps S Rem...

Page 24: ...e will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrug...

Page 25: ...Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from...

Page 26: ...will exit S Mount the trap externally to the bottom side of the unit using the 2 screws provided in the location shown S Cut the corrugated tube as shown in the illustration above Connect the corrugat...

Page 27: ...ig 18 that corresponds to the installation position of the furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe jo...

Page 28: ...til it bottoms out NOTE Cement MUST be fluid while inserting pipe If NOT recoat pipe 4 Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fittin...

Page 29: ...ng materials may be affected by flue products expelled in close proximity to unprotected surfaces Sealing or shielding of the exposed surfaces with a corrosion resistant material such as aluminum shee...

Page 30: ...Snow Level 36 Min 2 50 8mm Max 36 Min OR 914 4mm 914 4mm A07718 Fig 25 Concentric Vent and Combustion Air Roof Termination A Vent Dimension A is touching or 2 in 503 8mm maximum separation 25 22 02d...

Page 31: ...he installation from Table 4 and Fig 32 2 Determine the best location for the termination kit See Fig 31 for vertical termination or Fig 35 for horizontal termination Roof termination is preferred sin...

Page 32: ...Airflow restriction will occur and the furnace pressure switch may cause intermittent operation Drill clearance hole in rain cap and pilot hole in vent pipe Stainless steel screw Field supplied A07722...

Page 33: ...essures Combustion Air Vent Combustion Air Vent 45 Elbow Field Supplied 25 22 02 Strap Field Supplied Flush to 1 25 4mm max Note Securing strap must be field installed to prevent movement of termina t...

Page 34: ...in National Fuel Gas Code or CGA codes 3 Two stage regulation of Propane gas is recommended Propane Conversion FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or d...

Page 35: ...2 pressure switches Manual shut off valve Alternative installation Representative drawing only some models may vary in appearance A07724 Fig 36 Typical Gas Piping for Upflow Use elbows and 3 76 mm pip...

Page 36: ...s 6 and 7 Table 7 LPG or Propane Gas Manifold Pressure in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL Ft M 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000...

Page 37: ...injury and or loss of life WARNING 1 The furnace and the equipment shut off valve must be dis connected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 38: ...e 115V HUM called HUM on Control is energized when the inducer is energized ELECTRONIC AIR CLEANER EAC is energized when there is a blower speed call except is NOT energized when blower operates in th...

Page 39: ...ucts under the floor or through the attic 1 For side connections using a 16 x 25 406 x 635 mm filter cut out the embossed area shown in Fig 41 This will provide a 141 2 x 221 2 368 x 572 mm approxim a...

Page 40: ...unit to avoid condensation on the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the furnace This allows for installation in the horizontal right or...

Page 41: ...tent 1 Turn OFF gas supply to all appliances and start furnace Use jumper wire on R to W for Heat 2 Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution Re...

Page 42: ...inal will not be available at the Unused Motor Lead location Continuous Fan Operation using G Energizing the G terminal on the furnace control provides continuous fan operation This is done by connect...

Page 43: ...lve is energized the main burners light and flame is sensed S The igniter is de energized after the main burners ignite S FCB will delay blower operation for the 30 seconds timed from the opening of t...

Page 44: ...ger than two minutes 1 hr delay roll out switch requires manual reset 8 Flashes Permanent Lockout Gas valve relay contact stuck closed or miswired gas valve power reset only 10 Flashes Line voltage 11...

Reviews: