background image

II.

BLOWER MOTOR AND WHEEL MAINTENANCE

To ensure long life, economy, and high efficiency, clean accumu-
lated dirt and grease from blower wheel and motor annually.

The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.

The following items should be performed by a qualified service
technician.

Clean blower motor and wheel as follows:

1. Turn off electrical supply to furnace.

2. Remove main furnace door and blower access panel.

3. Disconnect blower motor wires from furnace control board.

Field thermostat connections may need to be disconnected
depending on their length and routing.

4. Remove control box mounting screws, and position control

box, transformer, and door switch assembly to right side of
furnace casing.

5. If condensate trap is located in left- or right-hand side of

furnace casing, proceed to item 6, otherwise remove trap
and tubing as described below. (See top left of Fig. 8.)

a. Disconnect field drain connection from condensate trap.

b. Disconnect drain and relief port tubes from condensate

trap.

c. Remove condensate trap from blower shelf.

6. Remove screws securing blower assembly to blower shelf

and slide blower assembly out of furnace.

7. Clean blower wheel and motor by using a vacuum with soft

brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades
as balance will be affected.

8. If greasy residue is present on blower wheel, remove wheel

from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly

to ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor shaft.

NOTE:

Mark blower mounting arms and blower housing so each

arm is positioned at the same hole location during reassembly.

c. Mark blower wheel orientation and cutoff plate location

to ensure proper reassembly.

d. Remove screws securing cutoff plate and remove cutoff

plate from housing.

e. Remove bolts holding motor mounts to blower housing

and slide motor and mounts out of housing. Disconnect
capacitor and ground wire attached to blower housing
before removing motor. Motor mounts need not be
removed from motor.

f. Remove blower wheel from housing.

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in noise or
furnace component failure.
The blower wheel should not be dropped or bent as
balance will be affected.

g. Clean wheel per instructions on degreaser cleaner. Do

not get degreaser cleaner in motor.

9. Reassemble motor and blower wheel by reversing items 8b

through 8f. Ensure wheel is positioned for proper rotation.
Be sure to reattach ground wire. Tighten setscrew to 140 to
160 in.-lb torque.

10. Reinstall blower assembly in furnace.

11. Reinstall control box, transformer, and door switch assem-

bly on blower shelf.

12. Reinstall condensate trap and tubing if previously removed.

a. Reinstall condensate trap in hole in blower shelf.

b. Connect condensate trap drain tubes. See Fig. 8 or tubing

diagram on main furnace door for proper tube location.

NOTE:

Ensure tubes are not kinked or pinched, as this will affect

operation.

(1.) Connect 1 tube (blue or blue and white striped)

from collector box.

(2.) Connect 1 tube (violet or unmarked) from inducer

housing.

(3.) Connect 1 tube (relief port, green or pink) from

collector box.

c. Connect field drain to condensate trap.

13. Reconnect wires.

Refer to furnace wiring diagram, and connect thermostat leads if
previously disconnected. (See Fig. 16.)

NOTE:

Refer to Table 1 for motor speed lead reconnection if

leads were not identified before disconnection.

CAUTION:

UNIT DAMAGE HAZARD

Failure to adjust the heating speed may shorten heat
exchanger life.
Heating speed selection MUST be adjusted to provide
proper temperature rise as specified on the rating plate.

WARNING:

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or death.
Blower access door switch opens 115-v power to furnace
control. No component operation can occur. Caution must
be taken when manually closing this switch for service
purposes.

14. Turn on electrical supply. Manually close blower access

door switch. Use a piece of tape to hold switch closed.
Check for proper rotation and speed changes by performing
a component self-test as shown at the bottom of SERVICE
label. (See Fig. 17.)

15. If furnace is operating properly, remove tape to release

blower access door switch, replace blower access door, and
replace main furnace door.

III.

CLEANING BURNERS

The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:

1. Turn off gas and electrical supplies to furnace.

2. Remove main furnace door.

COLOR

SPEED

FACTORY

ATTACHED TO

Black

High

Cool

Yellow (When Present)

Medium High

Spare

Blue

Medium Low

Heat

Red

Low

Spare

White

Common

Com

—4—

Summary of Contents for 340MAV J Series

Page 1: ...olatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 GENERAL 2 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 2 CARE AND M...

Page 2: ...ions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may dama...

Page 3: ...pipes annually 6 Check burners for cleanliness annually CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Be careful of sharp metal edges etc Use care and wear protective...

Page 4: ...e or furnace component failure The blower wheel should not be dropped or bent as balance will be affected g Clean wheel per instructions on degreaser cleaner Do not get degreaser cleaner in motor 9 Re...

Page 5: ...available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage per sonal injury or loss of life 18 Check for gas...

Page 6: ...G FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury death or property damage Never test for gas leaks with an open flame Use a commercially availabl...

Page 7: ...N CONDENSATE TRAP CAP Condensate Trap Factory Installed in Blower Shelf CONDENSATE TRAP COLLECTOR BOX TUBE GREEN Condensate Trap on LEFT Side Optional CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE PLUGGED EN...

Page 8: ...nd the crack c If replacement is required replace igniter on igniter bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter d To remove ign...

Page 9: ...s on IX WINTERIZING CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage Freezing condensate left in the furnace will damage the furnace If the furnace will...

Page 10: ...s Make sure limit switch wire does not contact any metallic component such as the gas valve It wire is shorted 3 amp fuse on furnace control board will open and the unit will not operate Fig 12 Contro...

Page 11: ...t Self Test WARNING UNIT MAY NOT OPERATE Failure to follow this warning could result in electrical shock personal injury or death Blower access panel door switch opens 115 v power to control board No...

Page 12: ...AFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTIN...

Page 13: ...g 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low in...

Page 14: ...ntire component test The HSI blower motor HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is doo...

Page 15: ...tricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition p...

Page 16: ...video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: