background image

To retrieve previous codes, remove 1 of the red main limit wires
for 1 to 4 sec until the LED light goes out, then reconnect it. (Do
not leave red wire disconnected for longer periods of time as the
control will assume an overtemperature condition exists and will
respond with blower operation.) This places the control in the
status recall mode and displays the first code stored in memory.
Record the code. After the last code is displayed the control will
perform the component test, and then return to normal standby
mode.

B.

Component Test

NOTE:

The furnace control component test allows all compo-

nents to run for a short time; except the gas valve and humidifier
terminal HUM are not energized for safety reasons. The EAC-1
terminal is energized when the blower is energized. This feature
helps diagnose a system problem in case of a component failure.
The component test feature will not operate if any thermostat
signal is present at the control and not until all time delays are
completed.

NOTE:

Record the status code BEFORE opening the blower

access door and before shutting off power to furnace. Opening the
blower access door will open the blower door switch and shut off
power within the furnace. When power to the furnace is shut off by
either method, the status code will be lost because the code is not
stored while power is removed for any reason.
To Begin Component Self-Test:

WARNING:

UNIT MAY NOT OPERATE

Failure to follow this warning could result in electrical
shock, personal injury, or death.
Blower access panel door switch opens 115-v power to
control board. No component operation can occur. Cau-
tion must be taken when manually closing this switch for
service purposes.

1. Remove blower access door.

2. Disconnect the thermostat R lead from furnace control

board.

3. Manually close blower door switch.

4. For approximately 2 sec, short (jumper) the C

OM

-24v

terminal on control to the TEST/TWIN 3/16-in. quick-
connect terminal on control until LED turns off. Remove
jumper from terminals. (See Fig. 12.)

NOTE:

If TEST/TWIN and C

OM

-24v terminals are jumpered

longer than 2 sec, LED will flash rapidly and ignore component
test request.

Component test sequence for single-stage furnace is as follows:

a. LED will display status code 11 four times.

b. Inducer motor starts and continues to run until Step f. of

component test sequence.

c. After 7 sec the hot surface igniter is energized for 15 sec,

then off.

d. Blower motor operates on HEAT speed for 10 sec.

e. Blower motor operates on COOL speed for 10 sec.

f. Inducer motor stops.

5. Reconnect R lead to furnace control board, remove tape

from blower door switch, and reinstall blower door.

6. Operate furnace per instruction on outer door.

7. Verify furnace shut down by lowering thermostat setting

below room temperature.

8. Verify that furnace restarts by raising thermostat setting

above room temperature.

A99118

Fig. 14—Inducer Housing Drain Cap

A99119

Fig. 15—Funnel in Drain and Antifreeze Running

Through Trap

—11—

Summary of Contents for 340MAV J Series

Page 1: ...olatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 GENERAL 2 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 2 CARE AND M...

Page 2: ...ions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may dama...

Page 3: ...pipes annually 6 Check burners for cleanliness annually CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Be careful of sharp metal edges etc Use care and wear protective...

Page 4: ...e or furnace component failure The blower wheel should not be dropped or bent as balance will be affected g Clean wheel per instructions on degreaser cleaner Do not get degreaser cleaner in motor 9 Re...

Page 5: ...available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage per sonal injury or loss of life 18 Check for gas...

Page 6: ...G FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury death or property damage Never test for gas leaks with an open flame Use a commercially availabl...

Page 7: ...N CONDENSATE TRAP CAP Condensate Trap Factory Installed in Blower Shelf CONDENSATE TRAP COLLECTOR BOX TUBE GREEN Condensate Trap on LEFT Side Optional CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE PLUGGED EN...

Page 8: ...nd the crack c If replacement is required replace igniter on igniter bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter d To remove ign...

Page 9: ...s on IX WINTERIZING CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage Freezing condensate left in the furnace will damage the furnace If the furnace will...

Page 10: ...s Make sure limit switch wire does not contact any metallic component such as the gas valve It wire is shorted 3 amp fuse on furnace control board will open and the unit will not operate Fig 12 Contro...

Page 11: ...t Self Test WARNING UNIT MAY NOT OPERATE Failure to follow this warning could result in electrical shock personal injury or death Blower access panel door switch opens 115 v power to control board No...

Page 12: ...AFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTIN...

Page 13: ...g 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low in...

Page 14: ...ntire component test The HSI blower motor HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is doo...

Page 15: ...tricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition p...

Page 16: ...video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: