background image

With power to the unit disconnected, check all electrical connec-
tions for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.

Reconnect electrical supply to unit and observe unit through 1
complete operating cycle for proper operation.

CAUTION:

UNIT

AND

PROPERTY

DAMAGE

HAZARD
Failure to follow this caution may result in furnace
component failures or water property damage.
If this furnace is to be operated in an unconditioned space
where the ambient temperatures may be 32°F or lower,
freeze protection measures must be taken. See Fig. 13.
See CONDENSATE DRAIN PROTECTION section of
Installation, Start-Up, and Operating Instructions.

VIII.

CHECKING HEAT TAPE OPERATION

(IF APPLICABLE)

In applications where the ambient temperature around the furnace
is 32°F or lower, freeze protection measures are required. If heat
tape has been applied, check to ensure it will operate when low
temperatures are present.

NOTE:

Heat tape, when used, should be wrapped around the

condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:

1. Check for signs of physical damage to heat tape such as

nicks, cuts, abrasions, gnawing by animals, etc.

2. Check for discolored heat tape insulation. If any damage or

discolored insulation is evident, replace the tape.

3. Check that heat tape power supply circuit is on.

IX.

WINTERIZING

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in furnace
component damage.
Freezing condensate left in the furnace will damage the
furnace.

If the furnace will be off for an extended period of time in a
structure where the temperature will drop to 32°F or below,
winterize as follows:

1. Turn off electrical supply to furnace.

2. Remove main furnace door.

3. Disconnect drain cap from unused drain tap on inducer

housing. (See Fig. 14.)

4. Connect field-supplied 1/2-in. I.D. tube to upper inducer

housing drain connection.

CAUTION:

UNIT DAMAGE HAZARD

Failure of plastic components may occur.
Do not use ethylene glycol (Prestone II antifreeze/coolant
or equivalent automotive type).

5. Insert funnel in tube and pour up to one quart of antifreeze,

propylene glycol (RV, swimming pool antifreeze, or
equivalent) into funnel until it is visible at point where
condensate enters open drain. (See Fig. 15.)

6. Reconnect drain cap to inducer housing.

7. Replace main furnace door.

8. Propylene glycol need not be removed before restarting

furnace.

WIRING DIAGRAM

See Fig. 16 for Wiring Diagram.

Fig. 11—Field Wiring

A02174

115-V FIELD-

SUPPLIED

DISCONNECT

AUXILIARY
J-BOX

24-V

TERMINAL

BLOCK

THREE-WIRE

HEATING-ONLY

FIVE WIRE

NOTE 1

NOTE 2

FIELD-SUPPLIED
DISCONNECT

CONDENSING
UNIT

TWO
WIRE

FURNACE

C
O
N

T

R
O

L

R

G

COM

W

C

R

G

Y

GND

GND

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING

208/230- OR
460-V
THREE
PHASE

208/230-V
SINGLE
PHASE

BLOWER DOOR SWITCH

WHT

BLK

WHT

BLK

NOTES:

Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.

W

Y

GND

THERMOSTAT
TERMINALS

1.
2.
3.

—9—

Summary of Contents for 340MAV J Series

Page 1: ...olatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 GENERAL 2 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 2 CARE AND M...

Page 2: ...ions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may dama...

Page 3: ...pipes annually 6 Check burners for cleanliness annually CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Be careful of sharp metal edges etc Use care and wear protective...

Page 4: ...e or furnace component failure The blower wheel should not be dropped or bent as balance will be affected g Clean wheel per instructions on degreaser cleaner Do not get degreaser cleaner in motor 9 Re...

Page 5: ...available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage per sonal injury or loss of life 18 Check for gas...

Page 6: ...G FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury death or property damage Never test for gas leaks with an open flame Use a commercially availabl...

Page 7: ...N CONDENSATE TRAP CAP Condensate Trap Factory Installed in Blower Shelf CONDENSATE TRAP COLLECTOR BOX TUBE GREEN Condensate Trap on LEFT Side Optional CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE PLUGGED EN...

Page 8: ...nd the crack c If replacement is required replace igniter on igniter bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter d To remove ign...

Page 9: ...s on IX WINTERIZING CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage Freezing condensate left in the furnace will damage the furnace If the furnace will...

Page 10: ...s Make sure limit switch wire does not contact any metallic component such as the gas valve It wire is shorted 3 amp fuse on furnace control board will open and the unit will not operate Fig 12 Contro...

Page 11: ...t Self Test WARNING UNIT MAY NOT OPERATE Failure to follow this warning could result in electrical shock personal injury or death Blower access panel door switch opens 115 v power to control board No...

Page 12: ...AFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTIN...

Page 13: ...g 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low in...

Page 14: ...ntire component test The HSI blower motor HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is doo...

Page 15: ...tricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition p...

Page 16: ...video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: