TROUBLESHOOTING

Use the Troubleshooting Guide, the status code LED on the
cotntrol and the Component Test to isolate furnace operation
problems.

A.

Status Codes

For an explanation of status codes, refer to service label located on
back of main furnace door or Fig. 17.

NOTE:

Removing the blower access door will open the blower

access door switch and terminate 115-v power to the control. This
will erase all stored status codes.

To read current status code, remove main furnace door. The status
code LED can be viewed through the sight glass in the blower
access door.

NOTE:

NO thermostat signals should be present at control and all

blower off delays must be completed to view previous codes.

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage to unit
components.
Make sure limit switch wire does not contact any metallic
component such as the gas valve. It wire is shorted,
3-amp fuse on furnace control board will open and the
unit will not operate.

Fig. 12—Control Center

A02100

BL
W

NUETRAL

ST
A

TUS CODE LED

SEC-2  SEC-1

EAC-2       L2

FUSE 3-AMP

0.5 AMP@24VAC

HUM

TEST/TWIN

    G     Com     

W        

Y        R

24V

120 180

90 150

BLOWER OFF-DELAY

PL
T                 1

COOL        HEA

T

SPARE-1  SPARE-2

EAC-1

1-AMP@

115VAC

PR-1

L1

PL2      1

24-V THERMOSTAT

TERMINALS

3-AMP FUSE

LED OPERATION &

DIAGNOSTIC LIGHT

115-VAC(L2)NEUTRAL

CONNECTIONS

COOL

HEAT

SPARE-1

SPARE-2

BLOWER SPEED

SELECTION TERMINALS

EAC-1 TERMINAL

(115-VAC 1.0 AMP MAX.)

115 VAC (L1) LINE

VOLTAGE CONNECTION

PL2-HOT SURFACE

IGNITER & INDUCER

MOTOR CONNECTOR

PL1-LOW VOLTAGE MAIN

HARNESS CONNECTOR

TRANSFORMER 24-VAC

CONNECTIONS

HUMIDIFIER TERMINAL

(24-VAC 0.5 AMP MAX.)

TWINNING AND/OR

COMPONENT TEST

TERMINAL

BLOWER OFF-DELAY

J2

J2 JUMPER

PL
T

A93058

32

°

F MINIMUM INSTALLED

AMBIENT OR FREEZE
PROTECTION REQUIRED

Fig. 13−Winterizing the Furnace

—10—

Summary of Contents for 340MAV J Series

Page 1: ...olatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 GENERAL 2 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 2 CARE AND M...

Page 2: ...ions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may dama...

Page 3: ...pipes annually 6 Check burners for cleanliness annually CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Be careful of sharp metal edges etc Use care and wear protective...

Page 4: ...e or furnace component failure The blower wheel should not be dropped or bent as balance will be affected g Clean wheel per instructions on degreaser cleaner Do not get degreaser cleaner in motor 9 Re...

Page 5: ...available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage per sonal injury or loss of life 18 Check for gas...

Page 6: ...G FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury death or property damage Never test for gas leaks with an open flame Use a commercially availabl...

Page 7: ...N CONDENSATE TRAP CAP Condensate Trap Factory Installed in Blower Shelf CONDENSATE TRAP COLLECTOR BOX TUBE GREEN Condensate Trap on LEFT Side Optional CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE PLUGGED EN...

Page 8: ...nd the crack c If replacement is required replace igniter on igniter bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter d To remove ign...

Page 9: ...s on IX WINTERIZING CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage Freezing condensate left in the furnace will damage the furnace If the furnace will...

Page 10: ...s Make sure limit switch wire does not contact any metallic component such as the gas valve It wire is shorted 3 amp fuse on furnace control board will open and the unit will not operate Fig 12 Contro...

Page 11: ...t Self Test WARNING UNIT MAY NOT OPERATE Failure to follow this warning could result in electrical shock personal injury or death Blower access panel door switch opens 115 v power to control board No...

Page 12: ...AFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTIN...

Page 13: ...g 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low in...

Page 14: ...ntire component test The HSI blower motor HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is doo...

Page 15: ...tricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition p...