Bryant 340MAV J Series Service And Maintenance Procedures Manual Download Page 8

15. Check for gas leaks.

16. Replace main furnace door.

VI.

SERVICING HOT SURFACE IGNITER

The igniter does NOT require annual inspection. Check igniter
resistance before removal.

1. Turn off gas and electrical supplies to furnace.

2. Remove main furnace door.

3. Disconnect igniter wire connection.

4. Check igniter resistance.

a. Using an ohm meter, check resistance across both igniter

leads in connector.

b. Cold reading should be between 45 ohms and 90 ohms.

c. If ohm reading is higher than 110 ohms, igniter is

cracked and must be replaced.

5. Remove igniter assembly.

CAUTION:

BURN HAZARD

Failure to follow this caution may result in minor
personal injury.
Allow igniter to cool before removal. Normal operating
temperatures exceed 2000°F.

a. Do not remove igniter from bracket while assembly is in

furnace. Using a 1/4 in. nutdriver, remove screw secur-
ing bracket and igniter assembly to bottom of burner
box. The screw in the bracket is always located toward
outside of burner box. The screw may be hidden by inlet
box or inlet pipe, but can be removed without removing
either. After removing screw, slide igniter and bracket
toward outside of burner box.

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in premature
failure of the igniter.
The igniter is fragile. DO NOT allow it to hit the side of
the burner box opening while removing or replacing it.

b. Inspect igniter for a white area indicating a crack may be

present. If found, replace igniter.

NOTE:

A small crack cannot be seen on a new igniter. After a

period of operation, a white area will be visible around the crack.

c. If replacement is required, replace igniter on igniter

bracket external to furnace to avoid damage as the
silicon portion is very brittle and will easily crack or
shatter.

d. To remove igniter from igniter bracket, remove screw

holding igniter ceramic block to bracket and slowly
work ceramic block out of bracket.

6. To replace igniter/igniter assembly, reverse items 5a

through 5d.

7. Reconnect igniter wire connection.

8. Turn on gas and electrical supplies to furnace.

9. Verify igniter operation by initiating furnace control board

self-test feature or by cycling thermostat.

10. Replace main furnace door.

VII.

ELECTRICAL CONTROLS AND WIRING

WARNING:

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or death.
There may be more than 1 electrical supply to the
furnace. Check accessories and cooling unit for additional
electrical supplies.

The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 11 for field wiring information
and to Fig. 16 for furnace wiring information.

NOTE:

If the polarity is not correct, the STATUS LED on the

furnace control board will flash rapidly and prevent the furnace
from operating. The control system also requires an earth ground
for proper operation of the furnace control and flame sensor.

The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control center. (See Fig. 12.) Any direct shorts of the 24-v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a 3-amp
fuse of identical size. The control LED will flash status code 24
when fuse needs to be replaced.

Fig. 9—Burner Flame

A89020

;;

;;

BURNER  FLAME

BURNER

MANIFOLD

Fig. 10—Gasket on Collector Box

A93081

RTV

PAM

—8—

Summary of Contents for 340MAV J Series

Page 1: ...olatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 GENERAL 2 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 2 CARE AND M...

Page 2: ...ions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may dama...

Page 3: ...pipes annually 6 Check burners for cleanliness annually CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Be careful of sharp metal edges etc Use care and wear protective...

Page 4: ...e or furnace component failure The blower wheel should not be dropped or bent as balance will be affected g Clean wheel per instructions on degreaser cleaner Do not get degreaser cleaner in motor 9 Re...

Page 5: ...available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage per sonal injury or loss of life 18 Check for gas...

Page 6: ...G FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury death or property damage Never test for gas leaks with an open flame Use a commercially availabl...

Page 7: ...N CONDENSATE TRAP CAP Condensate Trap Factory Installed in Blower Shelf CONDENSATE TRAP COLLECTOR BOX TUBE GREEN Condensate Trap on LEFT Side Optional CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE PLUGGED EN...

Page 8: ...nd the crack c If replacement is required replace igniter on igniter bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter d To remove ign...

Page 9: ...s on IX WINTERIZING CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage Freezing condensate left in the furnace will damage the furnace If the furnace will...

Page 10: ...s Make sure limit switch wire does not contact any metallic component such as the gas valve It wire is shorted 3 amp fuse on furnace control board will open and the unit will not operate Fig 12 Contro...

Page 11: ...t Self Test WARNING UNIT MAY NOT OPERATE Failure to follow this warning could result in electrical shock personal injury or death Blower access panel door switch opens 115 v power to control board No...

Page 12: ...AFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTIN...

Page 13: ...g 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low in...

Page 14: ...ntire component test The HSI blower motor HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is doo...

Page 15: ...tricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition p...

Page 16: ...video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: