If seal between the inducer housing and the collector box

is damaged in any way, it must be repaired. To repair, apply
sealant releasing agent such as PAM cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated
hydrocarbons, which could cause an inadequate seal to occur) to
inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV
162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove
in collector box.

11. Refer to furnace wiring diagram and reconnect wires to

inducer motor and pressure switch or connectors.

12. Reconnect pressure tubes to pressure switch. See diagram

on main furnace door for proper location of tubes. Be sure
tubes are not kinked. (See Fig. 8.)

13. Turn on gas and electrical supplies to furnace.

14. Check furnace operation through 2 complete heat operating

cycles. Check area below inducer housing, vent pipe, and
condensate trap to ensure no condensate leaks occur. If
leaks are found, correct the problem.

WARNING:

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result
in serious injury, death, or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage, per-
sonal injury, or loss of life.

Fig. 8—Furnace Pressure and Drain Tubing Diagram

A00308

Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.

Tube location when used in DOWNFLOW application

Tube location when used on

HORIZONTAL - RIGHT application

PLUG

CAP

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN TUBE

(BLUE)

INDUCER HOUSING DRAIN TUBE

(VIOLET)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN

TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX DRAIN TUBE

(BLUE)

INDUCER HOUSING (MOLDED) DRAIN TUBE

(BEHIND COLLECTOR BOX DRAIN TUBE)

FIELD-INSTALLED

FACTORY-SUPPLIED DRAIN TUBE

COUPLING (LEFT DRAIN OPTION)

FIELD-INSTALLED FACTORY-SUPPLIED

DRAIN TUBE

FIELD-INSTALLED

FACTORY-SUPPLIED 1/2-IN.

CPVC STREET ELBOWS (2)

FOR LEFT DRAIN OPTION

COLLECTOR BOX TUBE

(GREEN)

CONDENSATE  TRAP

CAP

Condensate Trap; Factory Installed

in Blower Shelf

CONDENSATE  TRAP

COLLECTOR BOX TUBE (GREEN)

Condensate Trap on LEFT

Side Optional

CAP

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUGGED END

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN TUBE

(BLUE)

COLLECTOR BOX TUBE

(GREEN)

CONDENSATE TRAP

INDUCER HOUSING DRAIN

TUBE (VIOLET)

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX DRAIN

TUBE

(BLUE & WHITE STRIPED)

Condensate Trap on

RIGHT Side

COLLECTOR BOX

EXTENSION DRAIN TUBE

DRAIN TUBE COUPLING

GAS VALVE

DRAIN TUBES ROUTED IN

FRONT OF GAS VALVE

PLUG

CAP

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

CONDENSATE TRAP

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

TUBE (GREEN)

INDUCER HOUSING

DRAIN TUBE

(VIOLET)

COLLECTOR BOX TUBE (PINK)

RELOCATE TUBE BETWEEN BLOWER

SHELF AND INDUCER HOUSING FOR

040,060, AND 080 HEATING INPUT

FURNACES

CAP

PLUG

COLLECTOR BOX DRAIN TUBE

(BLUE)

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX DRAIN TUBE

(BLUE AND WHITE STRIPED)

INDUCER HOUSING DRAIN TUBE (VIOLET)

CONDENSATE TRAP

Condensate Trap on

LEFT Side

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUG

Tube location when used in UPFLOW application

Tube location when used on

HORIZONTAL - LEFT application

CAP

PLUG

COLLECTOR BOX

EXTENSION TUBE

DRAIN TUBE

COUPLING

COLLECTOR BOX EXTENSION DRAIN TUBE

(Blower access panel removed)

1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to

 prevent a trap. Refer to the Installation Instructions for further details.

NOTE:

324999-201  REV. C

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE COUPLING

(RIGHT DRAIN OPTION)

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE PRESSURE

REFERENCE TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE PRESSURE

REFERENCE TUBE ASSEMBLY

TUBE ROUTING

AUXILIARY "J" BOX RELOCATED HERE

—7—

Summary of Contents for 340MAV J Series

Page 1: ...olatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 GENERAL 2 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 2 CARE AND M...

Page 2: ...ions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may dama...

Page 3: ...pipes annually 6 Check burners for cleanliness annually CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Be careful of sharp metal edges etc Use care and wear protective...

Page 4: ...e or furnace component failure The blower wheel should not be dropped or bent as balance will be affected g Clean wheel per instructions on degreaser cleaner Do not get degreaser cleaner in motor 9 Re...

Page 5: ...available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage per sonal injury or loss of life 18 Check for gas...

Page 6: ...G FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury death or property damage Never test for gas leaks with an open flame Use a commercially availabl...

Page 7: ...N CONDENSATE TRAP CAP Condensate Trap Factory Installed in Blower Shelf CONDENSATE TRAP COLLECTOR BOX TUBE GREEN Condensate Trap on LEFT Side Optional CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE PLUGGED EN...

Page 8: ...nd the crack c If replacement is required replace igniter on igniter bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter d To remove ign...

Page 9: ...s on IX WINTERIZING CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage Freezing condensate left in the furnace will damage the furnace If the furnace will...

Page 10: ...s Make sure limit switch wire does not contact any metallic component such as the gas valve It wire is shorted 3 amp fuse on furnace control board will open and the unit will not operate Fig 12 Contro...

Page 11: ...t Self Test WARNING UNIT MAY NOT OPERATE Failure to follow this warning could result in electrical shock personal injury or death Blower access panel door switch opens 115 v power to control board No...

Page 12: ...AFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTIN...

Page 13: ...g 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low in...

Page 14: ...ntire component test The HSI blower motor HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is doo...

Page 15: ...tricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition p...

Page 16: ...video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: